TECHNICAL DESCRIPTION
Kamstrup 162M/382M
5512-1040 GB/05.2012/Rev. C1
34
Manual scroll
In manual scroll there is the same list of available registers. Additional, two registers are only available for
manual scroll; Historical values and load profile.
Historical values (Debiting logger)
Load profile logger
From these display readings, it is possible to go to read out the register values in the meter’s memory by
activating the push button.
In the debiting logger it is possible to step through the values by a short push on the left pushbutton. For every
registration in the debiting logger, the following historical values are displayed:
OBIS code
Register
0. 9.2. XX
Date
0. 9.1. XX
Hour
96. 8.0. XX Hour counter
1. 8.0. XX
Active energy A+
1. 8.1. XX
Active energy A+ Tariff 1
1. 8.2. XX
Active energy A+ Tariff 2
1. 8.3. XX
Active energy A+ Tariff 3
1. 8.4. XX
Active energy A+ Tariff 4
2. 8.0. XX
Active energy A-
3. 8.0. XX
Reactive energy R+
4. 8.0. XX
Reactive energy R-
1. 6.0. XX
Peak power P+ max
1. 6.0. XX
Peak power P+ max date
1. 6.0. XX
Peak power P+ max hour
1. 6.1. XX
Peak power P+ max Tariff 1
1. 6.1. XX
Peak power P+ max Tariff 1 date
1. 6.1. XX
Peak power P+ max Tariff 1 hour
1. 6.2. XX
Peak power P+ max Tariff 2
1. 6.2. XX
Peak power P+ max Tariff 2 date
1. 6.2. XX
Peak power P+ max Tariff 2 time hour
1. 2.0. XX
Accumulated peak power P+ acc. max
0. 1.0. XX
Number of debiting periods
0.128.1. XX Pulse input
Table 16: Historical values shown in the display when reading out debiting logger.
It is possible to go to the next registration period by activating the push button approx. 2 seconds. “XX” indicates
from which period the data is. The latest (newest) log period has number 00 and the last (oldest) period can be
number 35.