TECHNICAL DESCRIPTION
Kamstrup 162M/382M
5512-1040 GB/05.2012/Rev. C1
39
6.2
Manual disconnection and connection
It is possible to disconnect the meter manually. This is done in the following way:
1a)
On the meter, select the below display reading by activating the left push button:
L1
L2
L3
1b)
Activate the left push button for approx. 6 secs. This will disconnect the relays, and the red diode turns on.
Manual reconnection is done in the following way:
2a) On the meter, select a display reading that is different from the reading selected in 1a).
2b)
Reconnection is possible when the diode emits green light and 1 minutes after disconnection.
Activate the left push button for 6 secs. until the relays are connected and the green diode is turned off. If
the relays are not connected after 6 secs., wait 1 min. and reactivate the left push button for 6 secs.
6.3
Disconnection by means of communication commands
Meters with breakers can also disconnect remotely via commands. Both the DLMS and KMP protocols permit to
disconnect, release and reconnect the supply to the consumer remotely via a communication network or locally
be means of e.g. the configuration tool METERTOOL.
There is a predefined 60 seconds hardware timer for the disconnection/connection function, meaning that you
must wait 60 seconds after a disconnection before the relays can be reconnected. The time is configurable, but
has to be 60 seconds as a minimum.