7.1
Maximum electrical rating values
Venkon XL, electromechanical version (115 V)
Size
Number
of fans
Rated
voltage
[VAC]
Power
fre-
quency
[Hz]
Rated
power
[W]
Rated
cur-
rent
[A]
Leakage
current
[mA]
Ri ana-
log in-
put
[KΩ]
MCA
MOP
Protec-
tion
class
Protec-
tion
class
1
1x Single
115
60
100
1.5
1.29
100
1.88
15
IP21
I
2
1x Tandem
115
60
170
2.5
1.29
100
3.13
15
IP21
I
3
1x Single,
1x Tandem
115
60
268
3.8
2.58
50
4.75
15
IP21
I
4
2x Tandem
115
60
342
4.8
2.58
50
6.00
15
IP21
I
Tab. 11: Maximum electrical connection values Venkon XL EC, electromechanical version (115 V)
Venkon XL, electromechanical version (208 V)
Size
Number
of fans
Rated
voltage
[VAC]
Power
fre-
quency
[Hz]
Rated
power
[W]
Rated
cur-
rent
[A]
Leakage
current
[mA]
Ri ana-
log in-
put
[KΩ]
MCA
MOP
Protec-
tion
class
Protec-
tion
class
1
1x Single
208
50
170
1.6
1.29
100
2.00
15
IP21
I
2
1x Tandem
208
50
200
1.8
1.29
100
2.25
15
IP21
I
3
1x Single,
1x Tandem
208
50
377
3.3
2.58
50
4.13
15
IP21
I
4
2x Tandem
208
50
412
3.5
2.58
50
4.38
15
IP21
I
Tab. 12: Maximum electrical connection values Venkon XL EC, electromechanical version (208 V)
Venkon XL, electromechanical version (240 V)
Size
Number
of fans
Rated
voltage
[VAC]
Power
fre-
quency
[Hz]
Rated
power
[W]
Rated
cur-
rent
[A]
Leakage
current
[mA]
Ri ana-
log in-
put
[KΩ]
MCA
MOP
Protec-
tion
class
Protec-
tion
class
1
1x Single
240
50
170
1.4
1.29
100
1.75
15
IP21
I
2
1x Tandem
240
50
247
2.0
1.29
100
2.50
15
IP21
I
3
1x Single,
1x Tandem
240
50
414
3.1
2.58
50
3.88
15
IP21
I
4
2x Tandem
240
50
489
3.7
2.58
50
4.68
15
IP21
I
Tab. 13: Maximum electrical connection values Venkon XL EC, electromechanical version (240 V)