Venkon
Assembly, installation and operating instructions
13
4
Technical data
Unit
Venkon AC
Model
61
63
66
67
Width of basic unit [mm]
625
925
1375
1725
Casing width [mm]
900
1200
1650
2000
Weight of basic unit [kg]
19
24.5
36.5
46.5
Air volume [m³/h]
125 – 530
240 – 705
350 – 1230
460 – 1510
Internal volume of 2-pipe
system [l]
1.3
2.0
3.1
3.9
Internal volume of 4-pipe
system [l] heating
0.5
0.6
0.9
1.1
Internal volume of 4-pipe
system [l] cooling
1.0
1.6
2.4
2.9
Heat output [kW]
2
1.54 - 7.74
2.89 - 10.65
4.01 - 17.74
5.44 - 23.21
Cooling output [kW]
1
0.79 - 3.27
1.43 - 4.52
1.86 - 7.67
2.72 - 10.19
Sound power level [dB(A)]
27 – 57
28 – 55
33 - 58
34 - 58
Unit
Venkon EC
Model
61
63
66
67
Length of basic unit [mm]
625
925
1375
1725
Casing length [mm]
900
1200
1650
2000
Weight of basic unit [kg]
19
24.5
36.5
46.5
Air volume [m³/h]
135 – 560
190 – 850
315 – 1405
355 – 1700
Internal volume of 2-pipe
system [l]
1.3
2.0
3.1
3.9
Internal volume of 4-pipe
system [l] heating
0.5
0.6
0.9
1.1
Internal volume of 4-pipe
system [l] cooling
1.0
1.6
2.4
2.9
Heat output [kW]
2
1.57 - 8.24
2.40 - 12.82
3.67 - 20.30
4.50 - 26.20
Cooling output [kW]
1
0.81 - 3.42
1.07 - 5.26
1.61 - 8.54
1.99 - 11.26
Sound power level [dB(A)]
28 – 61
23 – 58
29 - 62
27 - 61
Model
61
63
66
67
2
at LPHW 75 / 65°C, t
L1
= 20°C
1
at CHW 7/12°C, t
L1