Ensure that curtains, furniture and/or other combustible
materials are at a minimum distance of 150 cm from the
appliance.
* The floor the fireplace is placed on must be made of non-
combustible materials. The (combustible) floor in front of
the door opening must be protected (30 cm on both sides
and 50 cm in front of the appliance).
2.4.2 Installation of the Kalfire W65/38C in
combination with combustible materials
(e.g. a wooden wall)
When installing the Kalfire W65/38C pay attention to the distance
to combustible building materials:
Image: Cross-section of a corner Kalfire W65/38C
Combustible materials must be shielded by insulation material
with a minimum thickness of 5 cm. The distance from the back of
the fireplace to the combustible material must be a minimum of
10 cm.
* The floor the Kalfire W65/38C is placed on must be made
of non-combustible materials. The (combustible) floor in
front of the door opening must be protected to a distance
of at least 50 cm in front of the appliance (side/sides with a
glass door).
2.4.3 Installation of the Kalfire W90/47C in
combination with combustible materials
(e.g. a wooden wall)
When installing the Kalfire W90/47C pay attention to the distance
to combustible building materials:
Image: Cross-section of a corner Kalfire W90/47C
2.4.1 Installation of the Kalfire W front models in
combination with combustible materials
(e.g. a wooden wall)
When installing the fireplace, make sure to respect the recommended
distance from any combustible building materials:
Image: Cross-section of a front model Kalfire W
Combustible building materials behind the fire must also be
shielded or insulated by insulation material. The minimum
thickness (A) of the insulation material depends on the model
and type of fireplace. Refer to Table 1 for the required minimum
insulation thickness.
The distance from the back of the fireplace (or the side if the fire is
built into an alcove) to the insulation material must be a minimum
of 10 cm.
Ensure that windows are at a minimum distance of 100 cm
from the appliance.
11
Summary of Contents for W Series
Page 1: ...Installation and user manual CLOSED WOOD FIRES DON T COMPROMISE EN...
Page 2: ......
Page 4: ...4...
Page 6: ...6...
Page 49: ...Kalfire W60 51F All dimensions shown in mm Dimensions subject to modification 49...
Page 50: ...Kalfire W65 38CL All dimensions shown in mm Dimensions subject to modification 50...
Page 51: ...Kalfire W65 38CR All dimensions shown in mm Dimensions subject to modification 51...
Page 52: ...Kalfire W66 48S All dimensions shown in mm Dimensions subject to modification 52...
Page 53: ...Kalfire W70 33F All dimensions shown in mm Dimensions subject to modification 53...
Page 54: ...Kalfire W71 62F All dimensions shown in mm Dimensions subject to modification 54...
Page 55: ...Kalfire W80 52T All dimensions shown in mm Dimensions subject to modification 55...
Page 56: ...Kalfire W85 40F All dimensions shown in mm Dimensions subject to modification 56...
Page 57: ...Kalfire W90 47CL All dimensions shown in mm Dimensions subject to modification 57...
Page 58: ...Kalfire W90 47CR All dimensions shown in mm Dimensions subject to modification 58...
Page 59: ...Kalfire W90 47S All dimensions shown in mm Dimensions subject to modification 59...
Page 60: ...Kalfire W100 61F All dimensions shown in mm Dimensions subject to modification 60...
Page 61: ...Kalfire W105 47F All dimensions shown in mm Dimensions subject to modification 61...
Page 62: ...Kalfire W105 47T All dimensions shown in mm Dimensions subject to modification 62...
Page 63: ...Kalfire W120 38F All dimensions shown in mm Dimensions subject to modification 63...
Page 67: ......
Page 68: ...Gelo rveldweg 21 5951 DH Belfeld info kalfire nl KALFIRE COM DON T COMPROMISE REF V01 2018 EN...