background image

57

Before switching on the unit, read following recommenda-

tions:

The installer is obliged to verify correct operation of unit 

after installation.

11 TEST RUN AND FINAL 

    CHECKS

11.1 Final checks

When  the  complete  installation  and  all necessary 

settings have been carried out, close all front panels 

of the unit and refit the unit cover.
The service panel of the switch box may only be 

opened by a licensed electrician for

If required, the installer can perform a manual test run 

operation at any time to check correct operation of air 

purge, heating, cooling and domestic water heating, refer 

to 10.7 Field settings/test run.

11.2 Test run operation (manually)

That during the first running period of the unit, 

required power input may be higher than stated 

on the nameplate of the unit. This phenomenon 

originates from the compressor that needs 

elapse of a 50 hours run in period before 

reaching smooth operation and stable power 

consumption.

NOTE

In order to ensure optimal availability of the unit, a number 

of checks and inspections on the unit and the field wiring 

have to be carried out at regular intervals.
This maintenance needs to be carried out by your local 

technician.
In order to ensure optimal availability of the unit, a number 

of checks and inspections on the unit and the field wiring 

have to be carried out at regular intervals.
This maintenance has to be carried out by your local 

technician.

12 MAINTENANCE AND 

    SERVICE

DANGER

ELECTRIC SHOCK

Before carrying out any maintenance or 

repairing activity, must switch off the power 

supply on the supply panel.
Do not touch any live part for 10 minutes after 

the power supply is turned off.
The crank heater of compressor may operate 

even in standby.
Please note that some sections of the electric 

component box are hot.
Forbid touch any conductive parts.
Forbid rinse the unit. It may cause electric 

shock or fire.
Forbid leave the unit unattended when 

service panel is removed.

Make sure that the disposal of the glycol solution is done 

in accordance with relevant local laws and regulations.

Water pressure
Check the water pressure, if it is below 1 bar,fill water 

to the system.
Water filter
Clean the water filter.
Water pressure relief valve
Check for correct operation of the pressure relief 

valve by turning the black knob on the valve 

counter-clockWise:
-If you do not hear a clacking sound, contact your 

local dealer.
-In case the water keeps running out of the unit, close 

both the water inlet and outlet shut-off valves first and 

then contact your local dealer.
Pressure relief valve hose
Check that the pressure relief valve hose is 

positioned appropriately to drain the water.
Backup heater vessel insulation cover
Check that the backup heater insulation cover is 

fastened tightly around the backup heater vessel.
Domestic hot water tank pressure relief valve (field 

supply) Applies only to installations with a domestic 

hot water tank. Check for correct operation of the 

pressure relief valve on the domestic hot water tank.
Domestic hot water tank booster heater
Applies only to installations with a domestic hot water 

tank. It is advisable to remove lime buildup on the 

booster heater to extend its life span, especially in 

regions with hard water. To do so, drain the domestic 

hot water tank, remove the booster heater from the 

domestic hot water tank and immerse in a bucket (or 

similar) with lime-removing product for 24 hours.
Unit switch box
-Carry out a thorough visual inspection of the switch 

box and look for obvious defects such as loose 

connections or defective wiring.
-Check for correct operation of contactors with an 

ohm meter. All contacts of these contactors must be 

in open position.
Use of glycol (Refer to 9.3 Water pipework Caution: 

"Use of glycol" ) Document the glycol concentration 

and the pH-value in the system at least once a year.
-A PH-value below 8.0 indicates that a significant 

portion of the inhibitor has been depleted and that 

more inhibitor needs to be added.
-When the PH-value is below 7.0 then oxidation of the 

glycol occurred, the system should be drained and 

flushed thoroughly before severe damage occurs. 

The following checks must be performed at least once a 

year by qualified person.

58

When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no 

circumstances can safety devices be bridged or changed to a value other than the factory setting. If the cause of the problem 

cannot be found, call your local dealer.
If the pressure relief valve is not working correctly and is to be replaced, always reconnect the flexible hose attached to the 

pressure relief valve to avoid water dripping out of the unit!

Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects 

such as loose connections or defective wiring.

For problems related to the optional solar kit for domestic water heating, refer to the troubleshooting in the Installation 

& Owner's manual for that kit.

NOTE

When carrying out an inspection on the switch box of the unit, always make sure that the main switch of the unit is 

switched off.

WARNING

This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be carried out by your local technician.

13 TROUBLE SHOOTING

13.1 General guidelines

Symptom 2: The unit is turned on but the compressor is not starting (space heating or domestic water heating)

POSSIBLE CAUSES

CORRECTIVE ACTION

The unit must start up 

out of its operation range 

(the water temperature 

is too low).

In case of low water temperature, the system utilizes the backup heater to 

reach the minimum water temperature 

first (12°C).

•  Check that the backup heater power supply is correct.

•  Check that the backup heater thermal fuse is closed.

•  Check that the backup heater thermal protector is not activated.

•  Check that the backup heater contactors are not broken.

Symptom 1: The unit is turned on but the unit is not heating or cooling as expected

13.2 General symptoms

POSSIBLE CAUSES

CORRECTIVE ACTION

The temperature setting 

is not correct.

Check the controller set point.T4HMAX,T4HMIN in heat mode.

T4CMAX,T4CMIN in cool mode.T4DHWMAX,T4DHWMIN 

in DHW mode.

The water flow is too low.

•  Check that all shut off valves of the water circuit are 

    completely open.

•  Check if the water filter needs cleaning.

•  Make sure there is no air in the system (purge air).

•  Check on the manometer that there is sufficient water pressure. 

   The water pressure must be>1 bar (water is cold).

•  Make sure that the expansion vessel is not broken.

•  Check that the resistance in the water circuit is not too high 

   for the pump. 

The water volume in the 

installation is too low.

Make sure that the water volume in the installation is above 

the minimum required value (refer to "9.3 water piping/

Checking the water volume and expansion vessel pre-pressure").

63

62

Summary of Contents for KHC-22RY3

Page 1: ...INSTALATIONMANUAL MONO TYPE HEAT PUMP EN...

Page 2: ......

Page 3: ...HC 30RY3 PL KLIMATYZATOR CIENNY TYPU SPLIT Instrukcja obs ugi Dzi kujemy za wyb r naszego produktu Dla zapewnienia prawid owej obs ugi zapoznaj si z instrukcj i przechowuj j do wykorzystania w przysz...

Page 4: ...6 Application 7 8 1 8 2 8 3 8 4 8 5 8 6 8 7 Disassembling the unit Main components Electronic control box Water piping Adding water Water piping insulation Field wiring 9 1 9 2 9 3 9 4 9 5 9 6 9 7 Dim...

Page 5: ...Operation parameter Error codes 13 1 13 2 13 3 13 4 Initial start up at low outdoor ambient temperature Pre operation checks Powering up the unit Setting the pump speed Field settings 10 3 10 4 10 5...

Page 6: ...01 The picture and function described in this manual contain the backup heater components NOTE Wiring diagram Hydraulic System Refrigerant System Terminal Block Electric Control System 6...

Page 7: ...following types They are quite important so be sure to follow them carefully Meanings of DANGER WARNING CAUTION and NOTE symbols Indicates an imminently hazardous situation which if not avoided will...

Page 8: ...nd fire Make sure all wiring is secure Use the specified wires and ensure that terminal connections or wires are protected from water and other adverse external forces Incomplete connection or affixin...

Page 9: ...qualified person DISPOSAL Do not dispose this product as unsorted municipal waste Collection of such waste seperatelly for special treatment is necessary Do not dispose of electrical appliances as mu...

Page 10: ...p C Water flow temp C Outdoor temp C Water flow temp C Heat pump capacity Required heating capacity site dependent Additional heating capacity provided by backup heater Tbivalent Outdoor temperature C...

Page 11: ...nsions and heavy weight the unit should only be handled using lifting tools with slings The slings can be fitted into foreseen sleeves at the base frame that are made specifically for this purpose 4 B...

Page 12: ...nt local laws and regulations Don t install the unit near the sea or where there is corrosion gas When installing the unit in a place exposed to strong wind pay special attention to the following 6 IN...

Page 13: ...scribed below NOTE Construct a large canopy Construct a pedestal Install the unit high enough off the ground to prevent it from being buried in snow In case of strong wind and the wind direction can b...

Page 14: ...unit may not cause any vibrations or noise during its operation In accordance with the foundation drawing in the figure fix the unit securely by means of foundation bolts Prepare six sets each of 10...

Page 15: ...water can t drain out in cold weather NOTE 1 Single unit installation 2 Parallel connect the two units or above 3 Parallel connect the front with rear sides 600 3000 300 3000 1000 6000 4000 300 300 60...

Page 16: ...e 6 should be installed at the lowest positon of the system Pump_o 10 should be controlled by outdoor unit and connect to corresponding port in the outdoor unit refer to 9 7 6 Connection for other com...

Page 17: ...1 3 1 4 1 5 1 6 1 7 2 3 Assembly unit Assembly unit Coding Coding FHL 1 n 8 2 9 10 11 12 12 1 12 2 12 3 13 14 15 16 18 4 6 7 8 8 1 Drain valve Outdoor unit Manometer Pressure relief valve Expansion ve...

Page 18: ...heat pump If there is a huge demand for hot water or a high hot water tempera ture setting the booster heater 12 3 can provide auxiliary heating The unit can be configured so that at low outdoor temp...

Page 19: ...ating application by either the unit or by an auxiliary boiler connected in the system The unit controlled contact also called permission signal for the auxiliary boiler is determined by the outdoor t...

Page 20: ...for space heating only Be sure that the boiler and the integration of the boiler in the system is in accordance with relevant local laws and regula tions CAUTION FHL1 FHL2 FHLn 2 3 12 1 12 2 12 3 12 1...

Page 21: ...ape lter Stop valve eld supply Wired controller Drain valve eld supply Fill valve eld supply Balance tank eld supply Air purge valve 22 AHS Floor heating loop eld supply Expansion vessel eld supply P_...

Page 22: ...the field water circuit is the responsibility of the installer We only offer a dual set point control function This function allows two set points to be generated Depending on the required water temp...

Page 23: ...g temperature depends on which room thermostat is requesting heating When the room temperature of both zones is above the thermostat set point the outdoor unit and pump will stop operating 5A Room the...

Page 24: ...1 3 1 4 1 5 1 6 1 7 2 3 Assembly unit Assembly unit Coding Coding FHL 1 n 4 6 Outdoor unit Manometer Pressure relief valve Expansion vessel Plate heat exchanger Air purge valve Flow switch P_i Circula...

Page 25: ...alve 17 Additional heating source boiler eld supply Floor heating loop eld supply FCU 1 n Fan coil units eld supply 9 10 11 12 12 1 12 2 12 3 Expansion vessel eld supply P_o Outside circulation pump e...

Page 26: ...ay be hot Door 1 To access to the compressor and electrical parts and hydraulic compartment 1 1 9 10 11 12 2 12 1 2 4 5 7 8 3 6 Push the grill to the left until it stops then pull its right edge so yo...

Page 27: ...ng air in the water circuit will be automatically removes air from the water circuit Balances water system pressure Expansion vessel volume 8L Four temperature sensors determine the water and refriger...

Page 28: ...ank of up temp sensor 12 Port for balanced water tank of dowm temp sensor 13 Port for domestic hot water tank temp sensor 14 Port for outlet water for zone 2 temp sensor Port for solar panel temp sens...

Page 29: ...ion port U Input port for high pressure switch CN23 Power for switching power supply CN2 Port for communication with PCB B CN8 Input port P_in for IPM module Input port P_out for IPM module CN12 CN1 C...

Page 30: ...ming CN11 Port for outdoor ambient temp sensor and condenser temp sensor CN9 Port for low pressure switch and quick check CN29 8 10 11 DIP switch S5 S6 12 13 2 6 13 CN30 CN11 CN27 S3 CN37 CN20 CN8 CN5...

Page 31: ...E1 Power supply port for DC fan CN212 Power supply port for main control board CN30 Power ltering L1 L1 Power ltering L2 L2 Power ltering L3 L3 Port for communication with PCB B CN8 Power supply for P...

Page 32: ...2 3 6 7 8 9 10 11 17 4 The units are equipped with a water inlet and outlet for connection to a water circuit The units should only be connected to closed water circuits Connection to an open water c...

Page 33: ...is below the maximum allowed water volume 9 4 2 Water volume and expansion vessel pre pressure checks 7 m 7 m Installation height difference Water volume 230 L Water volume 230 L No pre pressuread ju...

Page 34: ...water volume in the water circuit is 100 L In this example no action or adjustment is required Example 2 The unit is installed at the highest point in the water circuit The total water volume in the w...

Page 35: ...ed Add glycol according to the table below If you add glycol to the water do NOT install freeze protection valves Possible conse quence Glycol leaking out of the freeze protection valves WARNING Ethyl...

Page 36: ...equirements from the table above with the specifica tions provided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer If the liquid in the system is frozen th...

Page 37: ...in contact with the piping particularly on the high pressure side Make sure no external pressure is applied to the terminal connectors When installing the ground fault circuit interrupter make sure t...

Page 38: ...Thermistor cable for Tw2 Boiler control cable Room thermostat cable User interface cable Solar energy kit signal cable AC 2 200mA AC 5 200mA AC 2 or 3 200mA a 2 200mA DC 2 b AC 2 200mA a 200mA a AC 2...

Page 39: ...that outside force cannot affect the terminals Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due to unavoid able reasons be sure to obse...

Page 40: ...Fuse Distribution box Distribution box Distribution box Distribution box The parallel system electrical control system connection diagram 3N Master unit Slave unit 1 H1 H2 Slave unit 2 H1 H2 Slave un...

Page 41: ...L2 3 H 4 C 5 6 1ON 7 1OFF 8 9 10 11 12 24 23 N 21 N 20 IBH1 19 18 13 14 L1 15 16 17 N 22 25 HT 29 30 31 DFT2 32 DFT1 26 R2 27 ASH1 28 ASH2 1 A 2 B 3 X 4 Y 5 E 6 P 7 Q 8 E 9 H1 10 H2 2ON2OFF P_c P_o P_...

Page 42: ...e cooling mode A 2 When unit detect voltage is 230VAC between H and N the unit operates in the heating mode A 3 When unit detect voltage is 0VAC for both side C N H N the unit stop working for space h...

Page 43: ...nt functions pumps Procedure Connect the cable to the appropriate terminals as shown in the picture Fix the cable with cable ties to the cable tie mountings to ensure stress relief When ROOM THERMOSTA...

Page 44: ...ontrol for more information Procedure Connect the cable to the appropriate terminals as shown in the picture Fix the cable with cable ties to the cable tie mountings to ensure stress relief 5 For tank...

Page 45: ...he unit has smart grid function there are two ports on PCB to connect SG signal and EVU signal as following 1 when EVU signal closed the unit operate as below DHW mode turn on the setting temperature...

Page 46: ...27 27 27 27 26 T4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 T1S 35 35 34 34 34 34 34 34 33 33 33 33 33 33 32 32 32 32 32 32 32 2 T1S 34 34 33 33 33 33 33 33 32 32 32 32 32 32 31 31 31 31 3...

Page 47: ...5 T4 22 22 T4 30 30 T4 1 T1S 16 11 8 5 2 T1S 17 12 9 6 3 T1S 18 13 10 7 4 T1S 19 14 11 8 5 T1S 20 15 12 9 6 T1S 21 16 13 10 7 T1S 22 17 14 11 8 T1S 23 18 15 12 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 1 T1...

Page 48: ...he backup heater type Refer to the wiring diagram Booster heater circuit breaker Do not forget to turn on the booster heater circuit breaker applies only to units with optional domestic hot water tank...

Page 49: ...0 40 50 60 70 80 90 100 110 120 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 ESP kPa Flow rate m3 h Available external static presurre VS Flow rate C2 C3 C1 Only have faults remedied by qualifi...

Page 50: ...power section Ambient temperature too high E36 Electronic faults Electronics defective The warning signal is indicated by the LED display The fault signal LED and the SSM relay do not respond The pump...

Page 51: ...e controller Unlock lock some functions such as DHW temperature adjusting OK Go to the next step when programming a schedule in the menu structure and confirm a selection to enter in the submenu of th...

Page 52: ...ADJUST 25 C FCU FLH 3 3 2 COOL MODE SETTING 2 11 T4C2 2 12 ZONE1 C EMISSION 2 13 ZONE2 C EMISSION ADJUST Go to MENU FOR SERVICEMAN 3 HEAT MODE SETTING Press OK The following pages will be displayed 10...

Page 53: ...g page will be displayed Homepage zone 1 2 Addition page zone 2 Double zone is effective In this case the setting value of zone 1 is T1S the setting value of zone 1 is TS The corresponding TIS2 is cal...

Page 54: ...HEATING SOURCE Press OK The following page will be dispayed The OTHER HEATING SOURCE is used to set the parameters of the backup heater additional heating sources and solar energy kit 10 7 7 Other HEA...

Page 55: ...the 2 way valve will close 60s later the pump in the unit PUMPI will operate for 10min during which the flow switch will not work After the pump stops the 3 way valve will close and the 2 way valve w...

Page 56: ...ed the page that specical function runs the wired controller do not locked Press to scroll the cursor to YES and press OK The test run will turn off During special function operating other functions W...

Page 57: ...RESTART function is used to select whether the unit reapplies the user interface settings at the time when power returns after a power supply failure 10 7 13 AUTO RESTART During floor drying all the...

Page 58: ...LIMITATION Go to MENU FOR SERVICEMAN 14 POWER INPUT LIMITATION 14 POWER INPUT LIMITATION 0 ADJUST 14 1 POWER INPUT LIMITATION 10 7 16 CASCADE SET How to set the CASCADE SET Go to MENU FOR SERVICEMAN...

Page 59: ...st 15 5 60 5 MIN 1 16 t_DI_MAX the maximum time that disinfection will last 210 90 300 5 MIN 1 17 t_DHWHP_RESTRICT he operation time for the space heating cooling operation 30 10 600 5 MIN 1 18 t_DHWH...

Page 60: ...R FLOW TEMP Enable or disable the WATER FLOW TEMP 0 NON 1 YES 1 0 1 1 5 2 ROOMTEMP Enable or disable the ROOMTEMP 0 NON 1 YES 0 0 1 1 5 3 DOUBLEZONE Enable or disable the ROOMTHERMOSTAT DOUBLE ZONE 0...

Page 61: ...FF M1 M2 Define the function of the M1M2 sw itch 0 REMOTE ON OFF 1 TBH ON OFF 2 AHS ON OFF 0 0 2 1 15 2 SMART GRID Enable or disable the SMART GRID 0 NON 1 YES 0 0 1 1 15 3 T1b Tw 2 Enable or disable...

Page 62: ...ne in accordance with relevant local laws and regulations Water pressure Check the water pressure if it is below 1 bar fill water to the system Water filter Clean the water filter Water pressure relie...

Page 63: ...s not starting space heating or domestic water heating POSSIBLE CAUSES CORRECTIVE ACTION The unit must start up out of its operation range the water temperature is too low In case of low water tempera...

Page 64: ...he water keeps running out of the unit close both the water inlet and outlet shut off valves first and then contact your local dealer POSSIBLE CAUSES CORRECTIVE ACTION Backup heater operation is not a...

Page 65: ...in DHW mode POSSIBLE CAUSES CORRECTIVE ACTION Surface of coil in the tank not large enough The same solution for Symptom 7 TBH or AHS not available Heat pump will stay in DHW mode untill t_DHWHP_MAX...

Page 66: ...ION FAILURE CAUSE AND CORRECTIVE ACTION Water flow fault E8 displayed 3 times 1 The wire circuit is short connected or open Reconnect the wire correctly 2 Water flow rate is too low 3 Water flow switc...

Page 67: ...hat there is sufficient water pressure The water pressure must be 1 bar 5 Check that the pump speed setting is on the highest speed 6 Make sure that the expansion vessel is not broken 7 Check that the...

Page 68: ...d the IPM module board should be replaced High temp protection of inverter module 1 Power supply voltage of the unit is low increase the power voltage to the required range 2 The space between the uni...

Page 69: ...is wet or there is water in remove the water make the connector dry Add waterproof adhesive 4 The T2 sensor failure change a new sensor The plate exchanger refrigerant outlet gas pipe temp sensor T2B...

Page 70: ...he communication system 5 Put the SW9 to on of the master unit Communication fault between main control board of hydrautic module and Ta room thermostart transfer PCB 1 temperature collecting plate is...

Page 71: ...r remove the obstruction Compressor overcurrent protection 1 The same reason to P1 2 Power supply voltage of the unit is low increase the power voltage to the required range Compressor discharge temp...

Page 72: ...rews The Thermal Conductive Adhesive is dry or drop Add some thermal conductive adhesive 10 The wire connection is loosen or drop Reconnect the wire 11 Drive board is defective replace a new one 12 If...

Page 73: ...compressor 4 Check the L1 L2 L3 power line connection between the inventer board and the Filter board 5 Check the inventer board DC bus low voltage protection from inverter module mostly when compres...

Page 74: ...put Expanssion vessel Volume Max operating pressure Pre charge pressure Weight Net weight 177kg Gross weight 206kg Connections Water inlet outlet Operation range water side Operation range air side he...

Page 75: ...o have an electrical supply to equipment during servicing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation 1...

Page 76: ...operation is absolutely vital if brazing operations on the pipe work are to take place Ensure that the outlet for the vacuum pump is not closed to any ignition sources and there is ventilation availa...

Page 77: ...transport regulations Marking of equipment using signs Compliance with local regulations Disposal of equipment using flammable refrigerants Compliance with national regulations Storage of equipment a...

Page 78: ...ANNEX A Refrigerant cycle 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Description Description Item 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Item Compressor 4 Way Valve Gas liquid separator Air side heat exchang...

Page 79: ...16125300002403 V C 79...

Page 80: ...kaisai com...

Reviews: