52
9. Troubleshooting
9.1 Indoor Unit Error Display
Operation lamp
Timer lamp
Display LED STATUS
☆
1 time
X
E0
Indoor unit EEPROM parameter error
☆
2 times
X
E1
Indoor / outdoor units communication error
☆
3 times
X
E2
Zero crossing signal detection error(only for
MS12FU-09HRDN1-QRC8W,
MS12FU-09HRDN1-QRC8GW,
MS12FU-12HRDN1-QRC8GW,
MS12F-24HRDN1-QRC8GW)
☆
4 times
X
E3
Indoor fan speed has been out of control
☆
5 times
X
E4
Open circuit or short circuit of indoor room temperature T1
sensor
☆
6 times
X
E5
Open circuit or short circuit of evaporator coil temperature
T2 sensor
☆
7 times
X
EC
Refrigerant Leakage Detection
☆
2 times
O
F1
Open circuit or short circuit of outdoor ambient T4
temperature sensor
☆
3 times
O
F2
Open circuit or short circuit of condenser coil temperature
T3 sensor
☆
4 times
O
F3
Open circuit or short circuit of compressor discharge T5
temperature sensor
☆
5 times
O
F4
Outdoor unit EEPROM parameter error
☆
6 times
O
F5
Outdoor fan speed has been out of control
☆
1 times
☆
P0
IPM malfunction or IGBT over-strong current protection
☆
2 times
☆
P1
Over voltage or over low voltage protection
☆
3 times
☆
P2
High temperature protection of compressor top diagnosis
and solution(Only for KFU-24HRFN1-QRC8W,
KFU-24HRFN1-QRD0GW and KFU-24HRDN1-QRC8GW
models)
☆
5 times
☆
P4
Inverter compressor drive error
O
(
light
)
X
(
off
)
☆(
flash
)
Summary of Contents for KFU-09HRDN1-QRC8GW
Page 1: ...12F INVERTER SERIES Service Manual 2013 12FSI A 1310...
Page 12: ...12 5 Wiring Diagram 5 1 Indoor Unit KFU 09HRDN1 QRC8W KFU 09HRDN1 QRC8GW...
Page 14: ...14 KFU 24HRDN1 QRC8GW...
Page 15: ...15 5 2 Outdoor Unit KOB 09HFN1 QRC8W KOB 09HFN1 QRD0GW...
Page 16: ...16 KOB 12HFN1 QRC8W KOC 18HFN1 QRC4W...
Page 17: ...17 KOB1 12HFN1 QRD0GW KOZ 18HFN1 QRD0GW KOC1 18HFN1 QRC8GW...
Page 18: ...18 KOF 24HFN1 QRC8W KOF 24HFN1 QRD0GW KOF 24HFN1 QRC8GW...
Page 28: ...28 5 Disconnect the charge hose from the vacuum pump...