6.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
●
Pressure in the system rises.
●
Operating current rises.
●
Cooling or heating efficiency drops.
●
Moisture in the refrigerant circuit may freeze and block capillary tubing.
●
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and evacuated
to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections by
a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have
leakage.
1. Air purging with vacuum pump
1)
Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and 3-way
valves are set to the closed position.
2)
Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3)
Connect the charge hose of handle hi connection to the vacuum pump.
4)
Fully open the handle Lo of the manifold valve.
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-0.1MPa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Summary of Contents for KFU-09HRDN1-QRC8GW
Page 1: ...12F INVERTER SERIES Service Manual 2013 12FSI A 1310...
Page 12: ...12 5 Wiring Diagram 5 1 Indoor Unit KFU 09HRDN1 QRC8W KFU 09HRDN1 QRC8GW...
Page 14: ...14 KFU 24HRDN1 QRC8GW...
Page 15: ...15 5 2 Outdoor Unit KOB 09HFN1 QRC8W KOB 09HFN1 QRD0GW...
Page 16: ...16 KOB 12HFN1 QRC8W KOC 18HFN1 QRC4W...
Page 17: ...17 KOB1 12HFN1 QRD0GW KOZ 18HFN1 QRD0GW KOC1 18HFN1 QRC8GW...
Page 18: ...18 KOF 24HFN1 QRC8W KOF 24HFN1 QRD0GW KOF 24HFN1 QRC8GW...
Page 28: ...28 5 Disconnect the charge hose from the vacuum pump...