48
8.4.3.5 Evaporator coil temperature protection
TEstop
T2
Resume
Off
Decrease
TEdown
TEnorm
Hold
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
8.4.4
Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between 17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-
only mode according to ΔT (ΔT =T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
1
℃
Cooling
-
1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15 minutes
and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
8.4.5
Drying mode
8.4.5.1
Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in
cooling mode.
8.4.5.2
Compressor running rules
Summary of Contents for KFU-09HRDN1-QRC8GW
Page 1: ...12F INVERTER SERIES Service Manual 2013 12FSI A 1310...
Page 12: ...12 5 Wiring Diagram 5 1 Indoor Unit KFU 09HRDN1 QRC8W KFU 09HRDN1 QRC8GW...
Page 14: ...14 KFU 24HRDN1 QRC8GW...
Page 15: ...15 5 2 Outdoor Unit KOB 09HFN1 QRC8W KOB 09HFN1 QRD0GW...
Page 16: ...16 KOB 12HFN1 QRC8W KOC 18HFN1 QRC4W...
Page 17: ...17 KOB1 12HFN1 QRD0GW KOZ 18HFN1 QRD0GW KOC1 18HFN1 QRC8GW...
Page 18: ...18 KOF 24HFN1 QRC8W KOF 24HFN1 QRD0GW KOF 24HFN1 QRC8GW...
Page 28: ...28 5 Disconnect the charge hose from the vacuum pump...