37
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules
The maximum operation frequency of compressor after starting submits to following rule.
50
49
45
44
41
40
33
32
Fmax=T4FREMAX1
T4
30
29
22
20
Fmax=T4FREMAX2
Fmax=T4FREMAX3
Fmax=T4FREMAX4
Fmax=T4FREMAX5
Fmax=T4FREMAX6
Fmax=T4FREMAX7
Meanwhile, the maximum frequency is limited by the indoor fan speed.
Indoor fan speed
Maximum frequency
High speed / turbo function
No limit
Silent mode
Fixed at F3
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7 minutes
according to the outdoor ambient temp. During the 7 minutes, the frequency limitation is active. 7 minutes later,
the compressor running frequency will be controlled as below: