Interval
Maintenance task
See chapter
SIGMA CONTROL dis‐
play
Up to 6,000 h
At least annually
Change the oil filter
SIGMA CONTROL dis‐
play
Up to 6,000 h
At the latest every 3 years
Change the oil separator cartridge
Change the cooling oil
Annually
Check that all electrical connections are tight
–
Check the safety relief valve
Check the overheating safety shutdown function
Check the cooler for leaks
h = operating hours
Tab. 47 Regular maintenance tasks
10.2.4 Cooling oil changing interval
Machine utilization and ambient conditions are important criteria for the number and length of the
change intervals.
Authorized KAESER Service representative will support you in determining appropriate inter‐
vals and provide information on the possibilities of oil analysis.
➤ Please observe national regulations regarding the use of cooling oil in oil-injected screw com‐
pressors.
➤ Check operating conditions and adjust intervals as necessary.
KAESER LUBRICANTS
SIGMA Lubricant
Description
Maximum Recommended Change Interval
First oil change
Subsequent oil change
M–460
ISO 46 Semi-Synthetic
Lubricant
2,000 Hours
3,000 Hours
S–460
ISO 46 Synthetic Lubri‐
cant
6,000 Hours
8,000 Hours
S–680
ISO 68 Synthetic Lubri‐
cant
6,000 Hours
8,000 Hours
FG–460
ISO 46 Food Grade
Synthetic Fluid
2,000 Hours
3,000 Hours
Tab. 48 Oil change intervals lubricants
10.2.5 Regular Service Work
The table below lists necessary service tasks.
➤ Only authorized KAESER Service representatives should carry out service work.
10 Maintenance
10.2 Maintenance Schedule
62
Service Manual Screw Compressor
ASD T Tri-Voltage
9_5721 06 USE
Summary of Contents for ASD 25
Page 1: ...Service Manual Screw Compressor ASD T Tri Voltage 9_5721 06 USE...
Page 2: ...Original instructions KKW SASD 1 00 en 01 SBA SCHRAUBEN TRI VOLTAGE T SC...
Page 8: ...List of Illustrations vi Service Manual Screw Compressor ASD T Tri Voltage 9_5721 06 USE...
Page 10: ...List of Tables viii Service Manual Screw Compressor ASD T Tri Voltage 9_5721 06 USE...