Voltage full scale setting
In
UH
and
UL model
s
(5 – 60 – 300V)
and
OH
and
OL model
s
(600 – 1000V)
SET
This is where the
4-digit password can be changed. When SET key is pressed,
0000 figure is displayed in the bottommost line and the screen begins to flash
more rapidly
.
The figure in the flashing digit may be set with
▼
and
▲
keys
and
SET key is pressed to pass to the next digit.
When all digits are completed the
new password becomes ready to use
.
SET
This function enables to return to factory settings. When SET key is
pressed, Fab Set Wait (wait) is displayed and
Fab Set Ok is displayed
when all settings are re
stored
to factory settings
.
SET
SET
SET
SET
SET
SET
Parity :
no , even , odd
Stop Bits :
May be set as
(1) , (1.5)
or
(2).
Baud rate:
It may be set as
2400,4800, 9600,19200,28800, 38400,57600
or
115200.
Device No :
001 .....255
SET
SET
SET
SET
Relay Contact Position :
nO (normally switched on)
nC (normaly switched off)
Remote Access Permit
on :
Access enabled
oFF : Access disabled
NOTE
: When Remote Access is (on) other parameters in the menu
becomes inaccessible and previously set parameters become
disabled. This relay output may only be used via remote access.
ALARM RELAY SETTINGS
MODBUS RTU SETTINGS
RETURN TO FACTORY SETTINGS
PASSWORD SETTINGS
VOLTAGE FULL SCALE SETTINGS
It should be defined according to the maximum value by which
measurement is to be made. It may be set as (5 – 60 – 300V) in
UH
and
UL
model
s and (600 – 1000V) in
OH
and
OL model
s
.
For ex:
if 30 Vdc will be
measured as maximum in the system then this value may be set as
60 V