PULSE OUTPUT SETTINGS

ANALOGUE OUTPUT SETTINGS

Analogue output enabled
Analogue output disabled

Analogue Output Permit 

Pulse Types

Pulse output disabled

Total energy

Export Ener

gy

Import Ener

gy

Analogue Parameters

Voltage

 (V)

Current

  (A)

Power

 (W)

Voltage output type

V

V

V

V

Current output type

mA

mA

The device allows the below 

parameters be set as analogue output

.

t (msn)

t (msn)

Ps

Ener

gy

5 – 24V

Max 30V

PuLS timE

 :

 P

ulse time

 (Ps)  

   

It may be set between 

50msn – 900 msn .

 

P

ulse 

OFF 

Time

 (Po) 

is fixed at 

 1000 msn.

dEAL

 :

 1 p

ulse equivalent energy

It may bet set between 

   0,1kWh – 1kWh – 10kWh – 100kWh –

10000kWh – 50000kWh  

Operation Range Setting

In this mode operation is carried out disregarding the symbol of 

the measured value

In this mode, measred value may be set between 

 (+) % 100 ....... 

This menu is displayed when PErC is selected in the 

Analog

ue measurement 

range

(An rAng)

. This screen does not appear in other modes

In this mode, output may be given at any value between (+) % 100 ....... (-) % 100 

for measured value 

Ps

Ps

dEAL
dEAL
dEAL

1000ms

1000ms

(%)

 Upper Limit

(%)

 Lower Limit

Exit from parameter 

programming menu

(-) % 100 and output is given accordingly

This will be described in 

details in the following menu below

.

In this mode output is given only for the measured values between 

(+) % 100  -  (-) % 100

. This mode is the same as the operation 

mode when 

(PerC) mod

e is set with the widest limits

.

NOTE1 :

 (%) Upper Limit Value should be greater than (%) Lower Limit Value

   (%) 

Upper Limit Value cannot be set as 

% 0

.

NOTE2 : 

When measured value is outside the (%) lower limit value, Analogue 

output will be V/1V or 0mA/4mA. Analogue output may be max. 6V, 12V, 

24mA.

Summary of Contents for DC-MULTISER-1UH-DIN

Page 1: ...1 1 1 2 1 1 1 2 1 1 1 2 1 1 DC MULTISER 2UH DIN DC MULTISER 2OH DIN DC MULTISER 2OL DIN DC MULTISER 2UL DIN Green Power Measurement Device Dimensions 105x90x59 mm Easy use via menus with shortcuts DC...

Page 2: ...f the system presents power quality problems insulation transformer or EMC filter should be used for auxiliary power supply Switch board cover or protection sheet With our DC MULTISER devices dc curre...

Page 3: ...t Connections AC DC AC DC Power Supply Relay Power Supply Digital Input Connections max 30Vdc Com DI2 Connect 1 5 2 5 mm cable Power Supply Optical Insulation Optik izolasyon DI1 Optical insulation An...

Page 4: ...eters menu At this stage HHHH is displayed in the line at the bottom of the screen while the password screen flashes When SET key is pressed 0000 figures are displayed in the most bottom line and the...

Page 5: ...arity no even odd Stop Bits May be set as 1 1 5 or 2 Baud rate It may be set as 2400 4800 9600 19200 28800 38400 57600 or 115200 Device No 001 255 SET SET SET SET Relay Contact Position nO normally sw...

Page 6: ...Momentary mode In this mode as an extra the time seen in the adjacent box is displayed It may bet set between 300 msn and 5000msn When alarm is set alarm relay remains pulled until the end of this tim...

Page 7: ...e Curr Over dELy It may be set between 1 300 sec If the measured voltage exceeds the set voltage value the relay contact is released at the end of the delay time Over Current Mistake Repair Time Curr...

Page 8: ...rrent Delay Time Curr Undr dELy It may be set between 1 300 sec If the measured current falls below set current value relay contact is released at the end of the delay time Low Current Mistake Repair...

Page 9: ...s disabled alarm relay releases Latch mode when alarm mode is set alarm relay is pulled Alarm relay remains pulled even the alarm is disabled If latch mode iset in models with alarm function alarm sho...

Page 10: ...disregarding the symbol of the measured value In this mode measred value may be set between 100 This menu is displayed when PErC is selected in the Analogue measurement range An rAng This screen does...

Page 11: ...utputs Measurement Value Analogue output value 2 5 V 5 V 5 V Voltage V 0 10 V Example 1 Voltage Full Scale Setting Analogue Parameters Voltage Output Type Analogue Operation range setting PERC PERC up...

Page 12: ...arm mode 10 sec 10 sec Over Current Set Value Curr Over Val Over Current Alarm Permit Curr Over EnbL Over Current Alarm Mode Setting Curr Over tYPE Over Current Delay Time Curr Over dELy Over Current...

Page 13: ...t Type Current Output Type Accuracy Load Capacity 0 10V 2 10V 0 5V 1 5V 0 20mA 4 20mA 0 2 In current type max load resistance 750 Ohm In voltage type load current max 20 mA Updating Duration 200ms 6 R...