Kaden Installation Manual |
5
CAUTION
Do not
install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around
the unit, it may cause fire.
Do not
operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can
cause electrical components to short circuit.
1. The product must be properly grounded at the time of installation, or electrical shock may occur.
2. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your
home and property.
Note about fluorinated gases
1. This air-conditioning unit contains fluorinated gases. For specific information on the type of gas and the amount, please
refer to the relevant label on the unit itself.
2. Installation, decommissioning, service, maintenance and repair of this unit must be performed by a licensed technician.
3. Product decommissioning and recycling must be performed by a licensed technician.
4. If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months.
5. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
6. Only ARC (Australian Refrigeration Council) licence holders can install and commission this air conditioner. This air
conditioner must be installed to meet the requirements of the current version of AS/NZS 5149. It is illegal to vent some
types of refrigerant to the atmosphere.
REFRIGERANT
This appliance uses R32 (difluoromethane) refrigerant, which is a flammable gas class 2.2 according to AS/NZS 5149 and must
be handled by a refrigeration mechanic with appropriate Australian refrigerant handling licence.
• WARNING risk of fire/flammable material. If the refrigerant is leaked, together with an external ignition source, there is
possibility of ignition.
• Read all the OPERATING INSTRUCTIONS carefully before operation.
• Service personnel are required to carefully read the OPERATING INSTRUCTIONS and INSTALLATION MANUAL
before operation.
• Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION MANUAL and the like.
Certain levels of refrigerant require minimum room sizes. Please ensure that these minimum room sizes are adhered to for
standard installations (up to 10m pipe length). If larger refrigerant charges than standard are used then please consult AS/NZS
60335.2.40 to determine the safe minimum floor area for the installation.
Make sure that the area has been made safe by having suitable ventilation and is free from ignition sources before charging or
recovering the charge of R32.
Summary of Contents for KSI Series
Page 44: ...kadenair com au...