9. Electrical checks
Electrical safety checks
After installation, confirm that all electrical wiring is installed
in accordance with local and national requirements, and
according to the Installation Manual.
Before test run
Check grounding work
Measure grounding resistance by visual detection and with
grounding resistance tester. Grounding resistance must be
less than 4 Ω.
During test run
Check for electrical leakage
During the test run, use an electroprobe and multimeter to
perform a comprehensive electrical leakage test.
If electrical leakage is detected, turn off the unit
immediately and call a licensed electrician to find and
resolve the cause of the leakage.
WARNING
– RISK OF
ELECTRIC SHOCK
All wiring must comply with local and national electrical
codes, and must be installed by a licensed electrician.