Shutdown/Disassembly
Page 50
Operating Instructions for Powador 7700-9600_EN
EN
EN
Authorised electrician
11
Shutdown/Disassembly
11.1 Shutting down the inverter
DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death may occur if the cables and terminals in the inverter are touched.
›
After shutdown, wait at least 30 minutes before working on the inverter.
DANGER
Destruction of the DC plug
DC plugs can be destroyed by arcing if disconnected while still live.
›
It is absolutely necessary that the shutdown sequence is carried out in the correct order.
Shutdown sequence
1. Switch off the grid voltage by turning off the external circuit breakers.
2. Disconnect the PV generator using the DC isolator switch.
DANGER! The DC cables are still live.
"
Ensure that there is no voltage present on the grid connection terminals.
11.2 Uninstalling the inverter
↻
Shut down the inverter.
1. Unlock and open the housing door.
2. Open the connection cover connection area.
3. Remove the interface cable.
4. Release the DC and AC cables from the connection terminals.
5. Open the cable fittings.
6. Pull out the cables.
»
The uninstallation of the inverter is complete. Continue with the disassembly.
11.3 Dismantling the inverter
↻
Shut down the inverter.
↻
Uninstall the inverter.
1. Remove the inverter fastening.
2. Securely pack up the inverter if it is to be used later or
dispose of the inverter in line with regulations.
12
Disposal
For the most part, both the inverter and the corresponding transport packaging are made from recyclable raw
materials.
Unit
: Do not dispose of faulty inverters or accessories together with household waste. Ensure that the old unit and
any accessories are disposed of in a proper manner.
Packaging
: Ensure that the transport packaging is disposed of properly.