Maintenance/Troubleshooting
Operating Instructions for KACO blueplanet 3.0-4.6 TL1
Page 49
Status
Display
Explanation
Action
FS
52
54
Grid failure:
mid-undervoltage
L1 / L2
String voltage L1 / L2 is below the set
maximum permissible string voltage
"
Notify your author-
ised electrician.
E
FS
57
Waiting for
reactivation
Waiting time of the inverter after a
fault.
Inverter does not switch on
again until the country-specific
time has elapsed.
FS
58
Overtemperature
Control card
The temperature inside the unit was
too high. The inverter switches off to
prevent damage to the hardware.
"
Provide for sufficient
ventilation.
E
OS
60
Generator
voltage too high
The inverter does not begin feeding
into the grid until the PV voltage falls
below a specified value.
-
-
OS
61
External
limit (%)
The external limit
Power control
was activated by the grid operator. The
inverter limits its power.
OS
63
Measured values
P(f )/frequency-dependent power reduction: Frequency-dependent
power reduction will be activated when the BDEW (German Association
of Energy and Water Industries) Medium Voltage Directive goes into
effect. Power reduction starts at a frequency of 50.2 Hz.
OS
64
Measured values
Output current limiting: The AC current is limited once the specified
maximum value has been reached.
FS
70
Fan error
The fan is malfunctioning.
"
Replace
defective fan
E
OS
74
External idle power
requirement
The grid operator limits the feed-in
power of the inverter.
-
-
FS
78
Resid. current shut-
down (AFI)
The integrated AC/DC-sensitive
residual current device registered an
non-permissibly high leakage current
going to PE.
"
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
OS
79
Insulation meas-
urement
PV generator’s insulation is being
measured
-
-
FS
81,
82,
83
Protection shut-
down line volt.
L1 L2, L3
Overvoltage has been detected on
a conductor. An internal protective
mechanism has disconnected the
device to protect it against damage.
"
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
FS
84
Protection shut-
down undervolt.
DC link
A voltage deviation has been found
in the DC link. An internal protective
mechanism has disconnected the
device to protect it against damage.
"
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
FS
85
Protection shut-
down overvolt. DC
link
E
FS
87
Protect. shutdown
overcurrent L1
A current that has been found on a
conductor is too high. An internal
protective mechanism has discon-
nected the device to protect it against
damage.
"
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
FS
97
Protection shut-
down overcurrent
HW
Too much power has been fed into the
grid. Complete disconnection of the
device.
"
Notify authorised
electrician / KACO
Service
E/K
Table 3:
Operating status and fault messages on the display