Installation
Page 18
Operating Instructions for KACO blueplanet 3.0-4.6 TL1
Authorised electrician
7 Installation
DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death may occur if the cables and terminals in the inverter are touched.
Only appropriately qualified and authorised electricians may open and install the inverter.
The inverter must be mounted in a fixed position before being connected electrically.
›
Observe all safety regulations and current technical connection specifications of the responsible
power supply company.
›
Disconnect the AC and DC sides.
›
Secure both sides against being inadvertently switched back on.
›
Ensure that the AC and DC sides are completely isolated and voltage free.
›
Connect the inverter only after the aforementioned steps have been taken.
7.1
Opening the connection area
NOTE
Only remove the cover for the connection area (blue). Opening the housing cover (grey) will invali-
date the warranty.
1
2
3
Figure 9: Disassemble the cover
Figure 10: Remove the cover
Figure 11: Remove the slider
Key
1
Screws for mounting (x2)
3
Slider
2
Cover for the connection area
Opening the connection area
ඣ
You have mounted the inverter on the wall.
1.
Set the DC isolator switch to "OFF".
2. Unscrew and remove the screws for fixing on the cover for the connection area.
3. Pull the cover downwards.
4. Pull the slider out and upwards.
»
Configure AC connector for connection.