Configuration and Operation
Page 38
Operating Instructions for KACO blueplanet 3.0-4.6 TL1
Country
-spec. setting
menu
level
Display/
setting
Action in this menu/meaning
DE, BE, GB, IL,
IT, JO, AT, CY,
UD
4
1
2
3
1
Connect time
"
Set period for grid observation (in seconds) when
switching on and reconnection after a fault.
IL, IT, UD
4
1
2
3
1
P(f) Gradient
"
Set gradient of power limit function with increasing
frequency in % / Hz. This percentage relates to the
nominal frequency of 50 Hz
4
1
2
3
1
P(f) thresholds
"
Set the frequency thresholds for activating and
deactivating the power limitation in Hz.
DE, AU, BE,
FR, GB, GR,
IL, IT, JO, NL,
AT, CY, UD
4
1
2
3
1
DC starting volt.
The inverter begins feed-in as soon as this DC voltage is
present.
"
Set the starting voltage.
DE, AU, BE,
FR, GB, GR,
IL, IT, JO, NL,
AT, CY, UD
4
1
2
3
1
Const. volt. ctrl.
Lets you deactivate the MPP seek mode in order to oper-
ate the inverter with a constant DC voltage.
"
Activate or deactivate function.
"
Set value for constant voltage control (125 - 510 V).
NOTE:
For voltages below the minimal MPP voltage the
possible input power is reduced. The input current is
limited here to 11A per input.
DE, AU, BE,
FR, GB, GR,
IL, IT, JO, NL,
AT, CY, UD
4
1
2
3
1
Power
limitation
The output power of the inverter can be set perma-
nently to a lower value than the maximum output
power by the internal power limiting. This may be nec-
essary in order to limit the maximum power rating of
the system at the grid connection point, upon the grid
operator's request.
The value can be protected from the very first output
limitation entry. After setting a limitation, the value can
only be changed by entering a device-specific password.
1.
Activate password protection if necessary.
2. Specify the activation status.
3. Specify the limit value for maximum feed-in power.
4. Confirm the entry with the OK button.
DE, AU, BE,
FR, GB, GR,
IL, IT, JO, NL,
AT, CY, UD
4
1
2
3
1
Powador-protect
Configures the support for grid shutdown by a Powador
protect connected to the digital input of the inverter.
ඣ
For Auto/On: A Powador protect is operating in
the photovoltaic system and is connected to the
inverter at the digital input/output.
"
Auto: The inverter automatically detects a Pow-
ador-protect integrated into the photovoltaic
system.
"
On: The digital signal of the Powador protect must
be present to the digital input of the inverter for the
inverter to start with feed-in.
"
Off: The inverter does not check whether a Pow-
ador-protect is integrated into the PV system.
DE, AU, BE,
FR, GB, GR,
IL, IT, JO, NL,
AT, CY, UD
4
1
2
3
1
Iso.resistor
"
Set threshold value (in 1 kOhm steps) at which the
insulation monitor reports a fault.