Country-
spec. Set-
tings
Me-
nu
level
Display/
Setting
Action in this menu/meaning
Activation threshold
with overfrequency
50.2 – 70 (Hz)
Activation threshold
with underfrequency
40 – 45 (Hz)
Activation threshold (f1) overfrequency:
Determines the frequency threshold for activating the function in case
of overfrequency incidents. The active power adjustment is activated if
the frequency rises above the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency falls below the
configured value.
Activation threshold (f1) underfrequency:
Determines the frequency threshold for activating the function in case
of underfrequency incidents. The active power adjustment is activated if
the frequency falls below the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency rises above the
configured value.
Retardo intenc.
0 – 5000 [ms]
The activation of the function based on the activation threshold is dela-
yed by the configured time.
Note 1: This function is regarded as critical for the stability of the trans-
mission grid and is therefore prohibited by several national grid connec-
tion regulations.
Note 2: This function is stipulated as a requirement by some domestic
grid connection directives in order to prevent any negative impact on is-
land detection. However, P(f) has no negative impact on KACO's enhan-
ced island detection.
Frequency of the maxi-
mum deactivation th-
reshold
45 - 50.2 (Hz)
Frequency of the mini-
mum deactivation th-
reshold
45 – 50.2 (Hz)
Deactivation range lower limit:
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the deactivation
range and remains in this range for the duration of the deactivation ti-
me.
Deactivation range upper limit:
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the deactivation
range and remains in this range for the duration of the deactivation ti-
me.
Tiempo de desact.
0 – 3600 [s]
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the range betwe-
en the minimum and maximum deactivation threshold and remains in
this range for the duration of the deactivation time.
Grad. de desact.
0 – 65534 [% / min]
If the available power is above the actual output at the time of deactiva-
tion, the power increase back to the maximum power is limited. The li-
mitation is implemented by an absolute power limitation that increases
with a continuous gradient up to the maximum power. The actual po-
wer of the inverter may vary freely below this limit due to a possible
fluctuation in the available power or the target value, but at no time in-
creases above the absolute power limit.