![Kaco blueplanet 29.0 TL3 M1 OD II4M Manual Download Page 54](http://html1.mh-extra.com/html/kaco/blueplanet-29-0-tl3-m1-od-ii4m/blueplanet-29-0-tl3-m1-od-ii4m_manual_649238054.webp)
4
1
2
3
4
Activation threshold
230V – 276V
F
Specify the activation threshold.
AVISO: If the 10 min mean value of the voltage exceeds the activation
threshold, then the function is enabled. The power level is adjusted in
such a way that the instantaneous effective voltage value does not ex-
ceed the activation threshold value.
4
1
2
3
4
Deactivation threshold
230V – 276V
AVISO: If the 10 min mean value of the voltage falls below the de-
activation threshold, then the function is disabled.
1 Specify the deactivation threshold.
4
1
2
3
4
Upload/download
AVISO: Opportunity to save log files and save and import parameter
data
Download service log
data
F
Save service log data to external storage media.
Download service log
data without yields
F
Save log data without yields to external storage media.
Download a set of pa-
rameters
F
Save a set of parameters to external storage media.
Document a set of pa-
rameters
F
Issue or print documentation of a set of parameters as a PDF.
Transfer a set of para-
meters
F
Load a set of parameters from external storage media.
AVISO
With regard to the selection of country settings, KACO new energy attests:
›
that the relevant certificates are only valid if the corresponding country settings have been selected.
›
that all configured grid parameters must be configured in accordance with the requirements of the
grid operators.
›
that the configuration of parameters using IEEE 1547: 2003 table 1 is possible but is only permitted if it
is requested by the grid operators.
9.5
Monitoring the device
The device has an integrated web server. This makes it possible to monitor and record the operating state and yield of
your PV system.
USB interface
Use an external USB storage device to read operating data saved on the device.
Reading log data
1 Connect a suitable USB storage device to the USB interface on the connection circuit board.
2 Open the “
Log data view
” menu.
3 Select "Save to USB".
4 Select the desired log data using the 4-way button.
5 Press the
Enter button
.
»
The device saves the selected log data to the USB storage device.
AVISO
The USB interface is approved solely for use with USB flash storage devices (“USB sticks”). The maximum
available current is 100 mA. If a device with a higher power requirement is used, the power supply for the
USB interface automatically shuts down to protect the device from damage.