Activation threshold
with overfrequency
50.2 – 70 (Hz)
Activation threshold
with underfrequency
40 – 45 (Hz)
1 Set frequency thresholds for activating the power limitation with
overvoltage.
2 Set the frequency thresholds for activating the power limitation
with undervoltage.
4
1
2
3
4
Gradiente salida ascen-
diente & Gradiente sa-
lida decreciente
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Power reduction P(U)
AVISO: To prevent the device from shutting down due to overvoltage
protection, the active power can be regulated in addition to reactive
power control in order to reduce the active power feed-in whereby
the output voltage is reduced.
4
1
2
3
4
P(U) modo de servicio
Off | On
F
Activate the control process.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to interfe-
rence.
4
1
2
3
4
Potencia de referencia
Potencia actual | Po-
tencia nominal
F
Select the power-dependent control method.
4
1
2
3
4
Tensión evaluada
Maximum phase vol-
tage | Positive phase
sequence voltage
F
Select the voltage to be rated.
Specifies which voltage is evaluated in a three-phase system.
4
1
2
3
4
Hysteresis mode
Off | On
AVISO: Hysteresis mode affects the shutdown response of P(U).
F
Activate the mode.
4
1
2
3
4
Deactivation gradient
0 – 65534 [% / min]
F
Set the gradients for the power limitation.
4
1
2
3
4
Deactivation time
0 – 60000000 [ms]
F
Specify the time for voltage reduction.
4
1
2
3
4
Gradiente salida ascen-
diente & Gradiente sa-
lida decreciente
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Tiempo de ataque
200 – 120000 [ms]
F
Specify the settling time.
4
1
2
3
4
Active curve
1 - 5
F
Select active curve.
AVISO: Up to 5 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
4
1
2
3
4
Núm. de pu. de ap.
2 - 5
F
Specify the number of nodes.
Power
0.0 – 100.0 [%]
F
Specify power for 1st, 5th ... node as a percentage of the maximum
power.
Voltage
0.0 – 126.0 [%]
Password protection
Status
1 Specify voltage for 1st, 5th ... node as a percentage of the maximum
voltage.
2 Activate optional password protection.
3 Confirm the action field.
Kaco blueplanet 29.0TL3