Country-
spec. Set-
tings
Me-
nu
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
10 p. apoyo Q(U)
F
Open the menu: Press the
Right arrow button
or
Enter
button
.
AVISO: More detailed information about the procedure can be found
at:
Reactive power control [Ver capítulo 10.1
4
1
2
3
4
Settling time
1s – 120 s
F
Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient res-
ponse corresponds to a first-order filter (PT-1) with settling time =
5Tau.
4
1
2
3
4
Potencia Lock-In
0 – 100% S
max
F
Set the active power as % of rated power above which control is acti-
vated.
4
1
2
3
4
Potencia Lock-Out
0-100% S
max
F
Set the active power as % of rated power below which control is de-
activated.
4
1
2
3
4
Hora Lock-In
0 s – 60 s
F
Set the length of time that the active power must remain below the
lock-in power level before control is activated.
4
1
2
3
4
Hora Lock-Out
0 s – 60 s
F
Set the length of time that the active power must remain below the
lock-out power level before control is deactivated.
4
1
2
3
4
Tiempo muerto
0 s – 10 s
F
Set the intentional delay for the start of the Q(U) function.
AVISO: If the voltage switches from a characteristic curve section with
Q=0 to a characteristic curve section with Q≠0 under active control,
then the reactive power setting process is delayed by the set dead ti-
me. Once the dead time has expired, the control circuit is no longer
subject to a delay and the set settling time determines the transient
behaviour.
4
1
2
3
4
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decrea-
sing
1 %-60000 %/min
AVISO: In addition to configuring the transient behaviour using the
settling time corresponding to a first-order filter, the reactive power
setting can be determined by a maximum gradient - maximum change
in the reactive power per time period.
F
Maximum change in the reactive power %Smax/min in the event of a
change to over-excited mode.
1 %-60000 %/min
F
Maximum change in the reactive power %Smax/min in the event of a
change to under-excited mode.
4
1
2
3
4
Cos-Phi Q1 mín. - Cos-
Phi Q4 mín.
AVISO: In the event of a significant voltage deviation, the maximum
reactive power adjustment range can be limited by a minimum cos φ
in order to prevent an excessive reactive power supply and, as a result,
a significant reduction in the maximum active power that can be fed
in.
F
Enter the minimum cos ϕ factor for quadrants 1 and 4.
4
1
2
3
4
Modo de prioridad
Q priority | P priority
F
Set priority for reactive power – Q or active power – P.
AVISO: When it comes to P priority, the reactive power adjustment
range is limited subject to the active power that is currently available
and fed in.
4
1
2
3
4
Curva activa
1 - 4
F
Select active curve.
AVISO: Up to 4 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
4
1
2
3
4
Restablecer curva
F
Reset active curve to the default setting.
Kaco blueplanet 29.0TL3
Página 47