B. The fire is off due to
little wood pellet can be
burned
The level of feeding
speed is too low
Adjust the combustion fan's speed Down
5 After ignition the power
is off 15min later.
Pellet feeder unit is off or
pellet is too little.
30˚C temperature switch
breaks or the connection
wires of switch loose.
Not enough pressure in
the stove
Check the pellet feeder unit and restart.
Check the connection wires or change the 30˚C temperature
switch.
Adjust the combustion fan's speed up
6 orange and lazy fire,
piled pellet, carbon on the
glass
Lack of air intake for
burning.
Clean the block in gate bar.
Check the door and window glass gasket sealed or not.
Check the air intake pipe and venting pipe blocked or not, and
clean it. Change to the big diameter pipes if pipes are too long
to affect combustion.
Adjust the combustion fan's speed up
Call the dealer to reset the program
7 The fire put out and
power is off automatically.
The hopper is empty.
No fuel feed.
The fuel feed is too little.
low temperature switch
(30˚C) is wrong.
Set temperature is
reached
Put fuel into the hopper. refer to (2)
Lower the speed of combustion fan
Cool the stove at least 1 hour then operate again or change the
low temperature switch (30˚C).
"ECO" its normal, waiting, after the temperature is blow set on,
it will automatically switch on again
8 The blower still works
after the stove is cool and
fuel feed stops.
The low temperature
switch (30˚C) is broken.
Change this switch.
9 no enough heat wind
Unqualified fuel
Blower speed is too high.
Use the standard specially pellet.
Use higher power