SHEVS Control Centre RWZ 1 b
11
Actuator output
Rated voltage
Mode of operation / duty cycle
Max. cross-section of supply line
Allowed voltage drop between Control Centre and actuator
Line monitoring (unbranched common line)
24
V
-
(+6
V / -4
V)
S3 30
%
2 x 10
mm² (rigid)
1
V at full load
wire-break, short-circuit
Allowed cable lengths with simple and moderately branched arrangement of the actuators
Current
Cross section
1.0 A
2.0 A
3.0 A
4.0 A
2 x 1.5 mm²
44 m
22 m
15 m
11 m
2 x 2.5 mm²
73 m
36 m
24 m
18 m
2 x 4.0 mm²
116 m
58 m
39 m
29 m
2 x 6.0 mm²
174 m
87 m
58 m
44 m
2 x 10.0 mm²
290 m
145 m
97 m
73 m
Fuses
Primary mains (miniature fuse 5 x 20
mm)
Accumulators (flat fuse 19
mm)
Actuators (flat fuse 19
mm)
F1: T 2
A
F2: 10
A
F3: 10
A
Alarm and malfunction forwarding (option PK)
Contact load rating PFC-
r
, PFC-
s
(change-over contacts)
Fuses PFC-
r
, PFC-
s
(miniature fuses 5 x 20
mm)
5
A / 30
V
-
/ 230
V~
P:F1, P:F2: F 5
A
Internal Wind and Rain Control (option WRM)
Wind sensor
WM
, heated rain sensor
RS
Adjustment range of sensitivity to wind
Adjustment range of sensitivity to rain
1 piece each
approx. 5 - 15
m/s (20 - 60
km/h,
approx. wind force 3 - 7)
light - stronger rain