background image

 

SHEVS Control Centre   RWZ  1 b 

 

 

 

8

 

3.8

 

Alarm and malfunction forwarding (option PK) 

 

PFC 

r

 (PFC alarm): The contact will be activated upon detection of an alarm. After resetting the alarm, the 

contact resets to its neutral position. 

 

PFC 

s

 (PFC malfunction): The contact is activated when a malfunction is detected (see 5). After eliminating 

the cause of malfunction, the contact resets to its neutral position. 

i

  The contacts are not enabled during alarm testing and maintenance mode. 

 
 

4

 

Maintenance 

  In the course of maintenance - unless other local regulations apply - check all functions and indicators of the 

Control Centre and its components at least once a year. This also includes the review of terminal points, con-
nection cables, indicators and fuses, as well as the cleaning of various components, if necessary. Check 
mounting brackets, etc. for proper fitting. Lubricate actuators and SHE vents (domelights, flap ventilators, lou-
vred ventilators etc.), if necessary. 
The individual functions of the Control Centre are described in section 3. Likewise, simulate malfunctions of 
the signal lines and power supply and check detection; see 5. 

 

Display of due maintenance 

If this function has been enabled by the maintenance company, the Control Centre indicates the due mainte-
nance through flashing of indicator 

9

 after about 11 months of operating time. After about 14 months mainte-

nance is overdue and a malfunction signal is generated additionally. 

 

Accumulators: 

  Check the accumulators 

at least once

 a year for proper functioning. They should be replaced following a 

typical service life of 3, but no more than 4 years in an ambient temperature of 20

°C. The service life falls 

by 1 year for every 10

°C rise in ambient temperature! 

 Checking the accumulators: Press the button 

Test

 

r

 in the Control Centre and then briefly press the but-

ton 

Reset

 

S

. This switches from mains to accumulator operation during the alarm test (actuators travel a 

bit slower). Open the actuators completely. If the accumulator voltage falls below 22.5

V, a malfunction is 

indicated. This indication continues until the button 

Reset

 

S

 is briefly pressed. 

After testing the accumulators, reset the alarm testing (press button 

Reset

 

r

 briefly) and close all actua-

tors again. 

i

  A quick check of the accumulators with less load takes place automatically every 15 minutes. 

  The end user, i.e. the final owner, must return used batteries / accumulators to a distributor or public 

waste management authority. This obligation to return applies regardless of whether it is a private or 
commercial end user. 

  If the system is put out of service / temporarily shut down, 

the accumulators must be unplugged

 and 

the line voltage switched off! 

  Charged accumulators that are not connected yet have a shelf-life of about 6 months. For longer storage, 

they must be recharged. 

!

 

When directly driving actuators

, e.g. with external accumulators during installation or maintenance work, 

the actuators must be disconnected from the Control Centre

! Otherwise, this can lead to defects in the 

power output of the Control Centre. 

 

Systems with internal wind and rain module (option WRM): 

Following inspections / work should be performed at least once a year: 

  Cleaning the rain sensor with a damp cloth, possibly with a mild detergent. 

Do not scour the sensor surface! 

  Check the wind sensor for smooth-running 

  Functional testing of the sensors 

  Check whether the SHE units and / or ventilation devices are properly closed 

 
 

Summary of Contents for GRASL SHEVS Control Centre RWZ 1 b

Page 1: ...Pneumatic Mechanik GmbH Europastraße 1 3454 Reidling Österreich Austria 43 0 22 76 21 200 0 43 0 22 76 21 200 99 _ Office graslrwa at www graslrwa at Smoke and Heat Ventilation Pneumatic Electronic Control Systems A530975 Installation and Operation Instructions Version 2 15 SHEVS Control Centre RWZ 1 b G 513007 0786 EN 12101 10 2005 Class A 0786 CPR 50643 14 ...

Page 2: ...es and Controls 4 3 1 Indicators control elements of the Control Centre 4 3 2 Selectable functions 5 3 3 Indicators functions of the manual call points 5 3 4 Alarm functions 5 3 4 1 Manual call points automatic fire detectors and Fire Alarm Control Panel 6 3 4 2 Repetition of OPEN cycle in case of alarm 6 3 5 Ventilation functions 6 3 5 1 Manual ventilation 6 3 5 2 Setting the ventilation position...

Page 3: ...ty actuators compatibility is to be checked Also note Section 6 Technical data Actuator specification 24 V actuators travelling time for full stroke at rated load total travelling time 4 min Actuators must be suitable for the repetition of OPEN and or CLOSE cycle see 3 4 2 3 6 Upon direct change of the sense of travel the actuators are briefly stopped before changing the sense Sheet steel enclosur...

Page 4: ...Control Centre and its components The individual functions are described in Section 3 also simulate malfunctions and check detection see 5 Following putting into service completely close all actuators if necessary press button z i After about 24 hours continuous operation without mains failure the accumulators are sufficiently charged to achieve the full standby time during mains failure 2 2 Putti...

Page 5: ...ee operation Extinguishes when a malfunction is detected r red RT 2 Alarm s yellow RT 2 BS Malfunction see also 5 Button Reset r red RT 2 BS Resetting the alarm function accessible after opening the door with a key Manual call point with buzzer S for audible alarm and malfunction signalisation RT 2 BS AA The buzzer emits a continuous warning tone in case of alarm and an intermittent warning tone i...

Page 6: ... tion position h see 3 5 2 Pressing it again stops the actuators By pressing the button for the reverse sense of travel the travel direction is reversed after a short stop When pressed longer 1 s the actuators travel as long as the button is pressed It can also be travelled up to the end position or the set ventilation position see 3 5 2 3 5 2 Setting the ventilation position h Set the travel time...

Page 7: ...g has no effect on sensitivity to constant wind Factory setting OFF normal sensitivity Perform the setting only for correspondingly stable or insensitive designs Continuous heating of rain sensor DIP switch W S1 2 In position ON the rain sensor is heated continuously at reduced power For example this reduces morning dew and incidental activation of the sensor If the sensor is activated by rain the...

Page 8: ...nt temperature of 20 C The service life falls by 1 year for every 10 C rise in ambient temperature Checking the accumulators Press the button Test r in the Control Centre and then briefly press the but ton Reset S This switches from mains to accumulator operation during the alarm test actuators travel a bit slower Open the actuators completely If the accumulator voltage falls below 22 5 V a malfun...

Page 9: ...Exception is the malfunction code U accumulator test failed also see 4 Accumulators and 5 2 This code has to be reset after troubleshooting by pressing the button Reset S 5 2 Indications of the service display With the help of the internal service display operating conditions can be accurately displayed In normal con dition there is no indication on the service display and the indicator o of the C...

Page 10: ...rotect from direct sunlight humidity and excessive formation of dust Preferably the installation should be carried out in dry heated rooms Signal lines Line monitoring wire break short circuit Line T Automatic fire detectors Smoke detector heat detector RM 2 TM 2 or RM 3 TM 3 or Fire Alarm Control Panel Terminating resistor Alarm resistor 20 pieces of which max 10 heat detectors 1 normally open co...

Page 11: ... x 2 5 mm 73 m 36 m 24 m 18 m 2 x 4 0 mm 116 m 58 m 39 m 29 m 2 x 6 0 mm 174 m 87 m 58 m 44 m 2 x10 0 mm 290 m 145 m 97 m 73 m Fuses Primary mains miniature fuse 5 x 20 mm Accumulators flat fuse 19 mm Actuators flat fuse 19 mm F1 T 2 A F2 10 A F3 10 A Alarm and malfunction forwarding option PK Contact load rating PFC r PFC s change over contacts Fuses PFC r PFC s miniature fuses 5 x 20 mm 5 A 30 V...

Page 12: ...les on following pages FACP F WRC r PFC s PFC System diagram please consider local conditions components r Smoke Exhaust r o s Smoke Exhaust r o s A S Smoke Exhaust Run the actuator lead unbranched to under the roof For max allowed lengths of cable please refer to section Technical Data Max 10 mm rigid can be clamped Page A 7 Page A 4 General length of cable max 400 m if not specified otherwise 2x...

Page 13: ... connect release resistor Ral 1k5 0 5 W affixed to Control Centre door when supplied as shown Main alarm point RT 2 BS Example of connection When connecting fire detectors remove terminating resistor Rab from Control Centre and connect it to the last detector Mains Actuators r o s Smoke Exhaust Ventilation buttons Remove link when con necting an external WRC WRC Link terminals 2 10 and 12 in the l...

Page 14: ...ors Rend from Control Centre and connect them to the last actuator Colour code for resistors 10k brown black black red When directly driving actuators e g with external accumulators during installation or maintenance work the actuators must be disconnected from the Control Centre In case of wrong travelling sense reverse polarity of actuator cable Run the actuator lead unbranched to under the roof...

Page 15: ...as shown Fire Alarm Control Panel FACP Ral 1k5 0 5 W FACP NO contact Additionally connect release resistor Ral affixed to Control Centre door when supplied as shown Automatic fire detectors or Fire Alarm Control Panel FACP Colour code for resistors 10k brown black black red 1k5 brown green black brown When connecting fire detectors remove terminating resistor Rab from Control and connect it to the...

Page 16: ... position open Colour code for resistors 10k brown black black red Manual call points When connecting fire detectors remove terminating resistor Rab from Control and connect it to the last detector 1st example Main alarm point last secondary alarm point last see page A 6 Terminals A H of the secondary alarm points are provided only for looping through the signals to following main alarm points Sec...

Page 17: ...lack black red 2nd example Secondary alarm point last main alarm point last see page A 5 Manual call points When connecting fire detectors remove terminating resistor Rab from Control and connect it to the last detector Terminals A H of the secondary alarm points are provided only for looping through the signals to following main alarm points Main alarm point RT 2 BS Main alarm point RT 2 BS AA A ...

Page 18: ...C NO NC C NO Potential free contacts option PK r r 1 2 3 1 2 3 4 5 6 4 5 6 s s F 1 2 3 4 5 6 Ventilation buttons Option PK 7 A 9 Ventilation buttons potential free contacts option PK Link terminals and P in the last ventilation button with indication of position OPEN Internal PFC relays Caution External voltage PFC PFC alarm r PFC PFC malfunction s ...

Page 19: ...hen connecting an external Wind and Rain Control Wind sensor WM 1 bk Surface of sensor External Wind and Rain Control WRS 2 Internal Wind and Rain Control option WRM Rain Sensor RS 2 Use a separate contact for each connected Control Centre Control Output contact 1 Output contact 2 Output contact 3 Output contact 4 x y Wind and Rain Control y 6 9 12 15 x 5 8 11 14 1 j 1 j w Q y y x x WRS 2 w w w rd...

Page 20: ...WZ 1 9 A 9 Accu Line voltage mounting accumulators Insert the accumulators in the enclosure secure them with the fastening plates and connect them as illustrated When putting into out of service observe the operating instructions Be sure to disconnect the accumulators if mains voltage supply is cut out for a longer time Accumulators Line voltage Mounting ...

Page 21: ......

Page 22: ......

Reviews: