Table 28: Site Electrical Wiring Guidelines
Site Wiring
Factor
Guidelines
Signaling
limitations
If your site experiences any of the following problems, consult experts in electrical surge
suppression and shielding:
•
Improperly installed wires cause radio frequency interference (RFI).
•
Damage from lightning strikes occurs when wires exceed recommended distances or pass
between buildings.
•
Electromagnetic pulses (EMPs) caused by lightning damage unshielded conductors and
electronic devices.
Radio
frequency
interference
To reduce or eliminate RFI from your site wiring, do the following:
•
Use a twisted-pair cable with a good distribution of grounding conductors.
•
If you must exceed the recommended distances, use a high-quality twisted-pair cable with
one ground conductor for each data signal, when applicable.
Electromagnet
ic
compatibility
If your site is susceptible to problems with electromagnetic compatibility (EMC), particularly
from lightning or radio transmitters, seek expert advice.
Strong sources of electromagnetic interference (EMI) can cause:
•
Destruction of the signal drivers and receivers in the device,
•
Electrical hazards as a result of power surges conducted over the lines into the equipment.
Rack Requirements
You can mount the device on two-post racks or four-post racks.
Rack requirements consist of:
• Rack type.
• Mounting bracket hole spacing.
• Rack size and strength.
90
Summary of Contents for EX4100
Page 1: ...EX4100 and EX4100 F Switch Hardware Guide Published 2022 11 08 ...
Page 68: ...Figure 45 Front to Back Airflow Through the EX4100 48P or EX4100 48T Switch Chassis 59 ...
Page 69: ...Figure 46 Front to Back Airflow Through the EX4100 24MP or EX4100 48MP Switch Chassis 60 ...
Page 70: ...Figure 47 Front to Back Airflow Through the EX4100 F 24P Switch Chassis 61 ...
Page 71: ...Figure 48 Front to Back Airflow Through the EX4100 F 24T Switch Chassis 62 ...
Page 72: ...Figure 49 Front to Back Airflow Through the EX4100 F 48P Switch Chassis 63 ...
Page 209: ...5 CHAPTER Troubleshoot Hardware Troubleshoot the EX4100 and EX4100 F Components 201 ...