SEE ALSO
Cabinet Requirements
You can mount the device in a cabinet that contains a 19-in. rack.
Cabinet requirements consist of:
• Cabinet size.
• Clearance requirements.
• Cabinet airflow requirements.
provides the cabinet requirements and specifications.
Table 30: Cabinet Requirements and Specifications
Cabinet Requirement
Guidelines
Cabinet size
•
The minimum cabinet size is 36 in. (91.4 cm) deep. Large cabinets
improve airflow and reduce chances of overheating.
Cabinet clearance
•
The outer edges of the front mounting brackets extend the width of the
chassis to 19 in. (48.2 cm).
•
The minimum total clearance inside the cabinet is 30.7 in. (78 cm)
between the inside of the front door and the inside of the rear door.