Lead acid batteries with armour plated cells and liquid
electrolyte
4.1
Description
Jungheinrich traction batteries are lead acid batteries with armour plated cells and
liquid electrolyte. The names of the traction batteries are PzS, PzB, PzS Lib and PzM.
Electrolyte
The rated density of the electrolyte assumes a temperature of 30°C and the rated
electrolyte level is fully charged. Higher temperatures will reduce, lower temperatures
will increase the electrolyte density. The adjustment factor is ± 0.0007 kg/l per K, e.g.
electrolyte density 1.28 kg/l at 45°C corresponds to a density of 1.29 kg/l at 30°C.
The electrolyte must conform to DIN 43530 Part 2 purity regulations.
4.1.1 Battery nominal data
1.
Product
Traction battery
2.
Nominal voltage
2.0 V x no. of cells
3.
Rated capacity C5
See data plate
4.
Discharge current
C5/5h
5.
Nominal electrolyte density
1
1. Reached within the first 10 cycles.
1.29 kg/l
6.
Nominal temperature
2
2. Higher temperatures shorten the useful life, lower temperatures reduce
the available capacity.
30 °C
7.
System rated electrolyte level
up to "Max" electrolyte level marking
Limit temperature
3
3. Not permissible as operating temperature.
55°C
03
.1
3 EN
4
4
Lead acid batteries with armour plated cells and liquid
electrolyte
4.1
Description
Jungheinrich traction batteries are lead acid batteries with armour plated cells and
liquid electrolyte. The names of the traction batteries are PzS, PzB, PzS Lib and PzM.
Electrolyte
The rated density of the electrolyte assumes a temperature of 30°C and the rated
electrolyte level is fully charged. Higher temperatures will reduce, lower temperatures
will increase the electrolyte density. The adjustment factor is ± 0.0007 kg/l per K, e.g.
electrolyte density 1.28 kg/l at 45°C corresponds to a density of 1.29 kg/l at 30°C.
The electrolyte must conform to DIN 43530 Part 2 purity regulations.
4.1.1 Battery nominal data
1.
Product
Traction battery
2.
Nominal voltage
2.0 V x no. of cells
3.
Rated capacity C5
See data plate
4.
Discharge current
C5/5h
5.
Nominal electrolyte density
1
1. Reached within the first 10 cycles.
1.29 kg/l
6.
Nominal temperature
2
2. Higher temperatures shorten the useful life, lower temperatures reduce
the available capacity.
30 °C
7.
System rated electrolyte level
up to "Max" electrolyte level marking
Limit temperature
3
3. Not permissible as operating temperature.
55°C
Summary of Contents for ERE 120n
Page 1: ...Operating instructions G Operating instructions 51159400 ERE 07 09 11 13 ERE 120n ...
Page 3: ...0108 GB ...
Page 7: ...0506 GB 2 ...
Page 9: ...0505 D A 2 ...
Page 14: ...B 5 0709 GB Dimensions sheet with fixed platform ...
Page 19: ...0709 GB B 10 ...
Page 29: ...0709 GB D 6 ...
Page 32: ...E 3 1113 GB 14 15 5 9 10 11 12 3 4 13 2 1 R V 8 8 7 7 6 ...
Page 34: ...E 5 1113 GB 14 15 5 9 10 11 12 3 4 13 2 1 R V 8 8 7 7 6 ...
Page 38: ...E 9 1113 GB 4 1 5 13 B B B F R V 0 3 2 R V ...
Page 57: ...1113 GB E 28 ...
Page 59: ...1113 GB E 30 ...