background image

3 Function 

Intended use 

Automatic switching of lighting depending on the heat motion and ambient brightness. 

Operation with flush-mounted insert for switching or dimming or 3-wire extension insert to 
expand the detection area. 

Ceiling installation on flush-mounted insert. 

Product characteristics 

Constant light control in combination with dimmer insert 

2-point light control in combination with switch insert 

Run-on time and brightness value settable 

Test operation for checking the detection area 

Push-on cover for limiting the detection area 

Expansion of the detection area in combination with 3-wire extension insert 

Manual switch-on and switch-off possible with 2-wire extension insert or installation button 

Automatic operation  

The presence detector detects heat motions of people, animals and objects. 

The light is switched on: 

If someone or something enters the monitored detection area and the brightness is below 
the set level. Dimmer inserts first switch to maximum brightness.  

The light remains switched on as long as motions are detected in the detection area and 
the brightness is not below the set level. 

The light is switched off: 

If no more movement is detected in the detection area and the run-on time has elapsed. 

If the brightness exceeds twice the set value for longer than 10 minutes. 

The minimum switch-off brightness is 400 lux, even if a lower value is set. 

The light is switched off in combination with dimmer inserts: 

If no more movement is detected in the detection area and the run-on time has elapsed. 
This is done by first dimming the light to minimum brightness and switching it off after 
5 minutes. 

If the light has been dimmed to minimum brightness and the brightness exceeds 1.5 times 
the set value for longer than 10 minutes. 

If the light was switched off because the brightness value was exceeded, the light control 
remains active. This means that the light is switched on again as the brightness decreases. 
With dimmer inserts, the light is switched on with minimum brightness. 

Expanding the detection area 

To extend the detection area, the presence detector cover is combined with a 3-wire extension 
insert and connected to a main device. The adjusters of the presence detector cover on the 3-
wire extension insert have no function. When motions are detected, the extension transmits a 
signal to the main device. 

Do not connect any main devices in parallel. 

Behaviour in case of a mains failure 

Less than 0.2 seconds: the old switching position is restored after mains return. 

Longer than 0.2 seconds: a self-test is performed after mains return. This takes approx. 
30 seconds. The light is switched on during the self-test; operation via extensions is not 
possible. 

4 Operation 

Switching on the light 

A 2-wire extension or an installation button is connected. 

Press button for less than 0.4 seconds. 
The light is switched on for at least 2 minutes. 

2/8 

82542823 
J:0082542823 

18.09.2012 

Light Management  

Presence detector universal 

Summary of Contents for PMU 360 WW

Page 1: ...lly isolated from the mains even when the device is switched off Danger of electric shock Always disconnect before carrying out work on the devise or load At the same time take into account all circuit breakers that supply dangerous voltage to the device or load Do not press on the sensor window Device can be damaged The device is not suitable for use as a burglar alarm or other alarm These instru...

Page 2: ...set The light is switched off in combination with dimmer inserts If no more movement is detected in the detection area and the run on time has elapsed This is done by first dimming the light to minimum brightness and switching it off after 5 minutes If the light has been dimmed to minimum brightness and the brightness exceeds 1 5 times the set value for longer than 10 minutes If the light was swit...

Page 3: ...the 2 wire extension or the the installation button Switching off the brightness evaluation The brightness evaluation can be switched off if the brightness is perceived as too dark after the light is switched off A 2 wire extension or an installation button is connected The presence detector has switched the light off due to adequate extraneous light e g daylight o Press the installation button wi...

Page 4: ...environment Selecting the installation location Figure 2 The presence detector is installed on the ceiling and monitors the surface under it figure 2 The presence detector has a detection area of 360 Die PIR sensor system operates with 6 detection levels and 80 lenses Figure 3 Detection field The range is approx 5 m in diameter at table height e g approx 80 cm At floor level the range diameter is ...

Page 5: ...ttered light o Connect flush mounted insert properly and mount in accordance with the desired orientation of the presence detector see instructions for flush mounted insert o Fit presence detector cover on flush mounted insert 5 2 Commissioning Testing the detection area The presence detector is mounted and connected properly o Pull off decor ring 3 o Set lux adjuster to3 figure 1 The presence det...

Page 6: ... set to the current brightness i If lux adjuster is on 0 the presence detector only switches on through operation of an extension In this case the switch off brightness is 400 lux o Attach decor ring 3 Calibrating the brightness value in combination with switch insert Brightness calibration is necessary to prevent light oscillations from occurring A light oscillation occurs when the presence detec...

Page 7: ...is on 0 the presence detector only switches on through operation of an extension In this case the switch off brightness is 400 lux o Attach decor ring 3 Setting the run on time The fewer the motions expected in the monitored area the longer the run on time setting should be This reduces the probability that the presence detector will switch off even though people are present Use 10 minutes as the ...

Page 8: ...ector see Connecting presence detectors in parallel Run on time too short Motion of persons is not detected Extend run on time using time adjuster see Setting the run on time Presence detector switches on and of constantly time adjuster is set to test Set run on time using time adjuster see Setting the run on time Presence detector switches off briefly and then on again immediately Brightness drop...