Turn 

lux

 adjuster in 

3

 direction (see Calibrating the brightness). 

Switched off via extension. 

Switch on via extension. 

Presence detector switches on without any detectable motion 

Interference sources in the detection area. 

Pay attention to interference sources, e.g. heating, ventilation, air conditioners, cooling light 
bulbs in the detection area.
Possibly limit detection area with the push-on cover (see Limiting the detection area). 

Presence detector does not switch off even when there is a great deal of extraneous 
light. 

The brightness value setting is too high. 

Turn 

lux

 adjuster in 

2

 direction (see Calibrating the brightness value). 

Presence detector switches off, even though people are present and the brightness is 
too low 

Detection problem, the surface to be monitored is not in the detection area, or furniture or pillars 
are in the way. 

Use an additional presence detector (see Connecting presence detectors in parallel). 

Run-on time too short. Motion of persons is not detected. 

Extend run-on time using 

time

 adjuster (see Setting the run-on time). 

Presence detector switches on and of constantly 
time

 adjuster is set to 

test

Set run-on time using 

time

 adjuster (see Setting the run-on time). 

Presence detector switches off briefly and then on again immediately 

Brightness drops below the brightness value setting after switch-off. 

Turn 

lux

 adjuster in 

3

 direction (see Commissioning section) 

6.3 Warranty 

We reserve the right to make technical and formal changes to the product in the interest of 
technical progress. 
We provide a warranty as provided for by law. 
Please send the unit postage-free with a description of the defect to our central customer 
service office. 

ALBRECHT JUNG GMBH & CO. KG 

Volmestraße 1 
58579 Schalksmühle 

Telefon: +49.23 55.8 06-0 
Telefax: +49.23 55.8 06-2 04 
[email protected] 
www.jung.de 

Service Center 

Kupferstr. 17-19 
44532 Lünen 
Germany 

8/8 

82542823 
J:0082542823 

18.09.2012 

Light Management  

Presence detector universal 

Summary of Contents for PMU 360 WW

Page 1: ...lly isolated from the mains even when the device is switched off Danger of electric shock Always disconnect before carrying out work on the devise or load At the same time take into account all circuit breakers that supply dangerous voltage to the device or load Do not press on the sensor window Device can be damaged The device is not suitable for use as a burglar alarm or other alarm These instru...

Page 2: ...set The light is switched off in combination with dimmer inserts If no more movement is detected in the detection area and the run on time has elapsed This is done by first dimming the light to minimum brightness and switching it off after 5 minutes If the light has been dimmed to minimum brightness and the brightness exceeds 1 5 times the set value for longer than 10 minutes If the light was swit...

Page 3: ...the 2 wire extension or the the installation button Switching off the brightness evaluation The brightness evaluation can be switched off if the brightness is perceived as too dark after the light is switched off A 2 wire extension or an installation button is connected The presence detector has switched the light off due to adequate extraneous light e g daylight o Press the installation button wi...

Page 4: ...environment Selecting the installation location Figure 2 The presence detector is installed on the ceiling and monitors the surface under it figure 2 The presence detector has a detection area of 360 Die PIR sensor system operates with 6 detection levels and 80 lenses Figure 3 Detection field The range is approx 5 m in diameter at table height e g approx 80 cm At floor level the range diameter is ...

Page 5: ...ttered light o Connect flush mounted insert properly and mount in accordance with the desired orientation of the presence detector see instructions for flush mounted insert o Fit presence detector cover on flush mounted insert 5 2 Commissioning Testing the detection area The presence detector is mounted and connected properly o Pull off decor ring 3 o Set lux adjuster to3 figure 1 The presence det...

Page 6: ... set to the current brightness i If lux adjuster is on 0 the presence detector only switches on through operation of an extension In this case the switch off brightness is 400 lux o Attach decor ring 3 Calibrating the brightness value in combination with switch insert Brightness calibration is necessary to prevent light oscillations from occurring A light oscillation occurs when the presence detec...

Page 7: ...is on 0 the presence detector only switches on through operation of an extension In this case the switch off brightness is 400 lux o Attach decor ring 3 Setting the run on time The fewer the motions expected in the monitored area the longer the run on time setting should be This reduces the probability that the presence detector will switch off even though people are present Use 10 minutes as the ...

Page 8: ...ector see Connecting presence detectors in parallel Run on time too short Motion of persons is not detected Extend run on time using time adjuster see Setting the run on time Presence detector switches on and of constantly time adjuster is set to test Set run on time using time adjuster see Setting the run on time Presence detector switches off briefly and then on again immediately Brightness drop...