KNX/EIB
Product documentation
Page: 24 of 29
Hardware description
Function: Shutter
Key function.
1/3 = UP, 2/4 = DOWN
1/3 = DOWN, 2/4 = UP
Defines the command transmitted on pressing
of the keys.
Number of steps before
continuous run (1...30)
1 ... 30;
1
A short-time telegram (STEP) permits adjusting
the slats of a shutter.
This parameter defines how many short-time
telegrams are transmitted before a continuous
run (MOVE) after a long key-press.
Time between two
telegrams, base
0.5 ms;
8 ms
; 130 ms;
2.1 s; 33 s
Defines the time base between two telegrams.
(Time between STEP – STEP or between STEP
– MOVE)
Time = base
•
factor
Time between two
telegrams, factor(2...255)
2 ... 255;
46
Defines the time factor between two telegrams.
(Time between STEP – STEP or between STEP
– MOVE)
Time = base
•
factor
Presetting: 8 ms
•
46 = 368 ms
Software remarks
•
For editing all of the parameters, the access must be set to "full access".
•
The status LED indicates either the current status of the switching object or a key-press. If a key is pressed
(e.g. ON) and if the push button sensor does not get a positive acknowledgement (IACK) from an addressed
actuator, the object status is updated and the corresponding status LED is lit up.