KNX/EIB
Product documentation
Page: 6 of 29
Hardware description
Application:
2.
Switching, acknowledgement 100A12
Executable from mask version:
1.0
Number of addresses (max):
8
dynamic table handling:
Yes
:
No
Number of assignments (max):
9
maximum length of table:
17
Communication objects
2
Object
Function
Name
Type
Flag
0 Switching
Rocker 1
1 bit
C, W, T
1 Switching
Rocker 2
1 bit
C, W, T
Object description
Objects:
0 - 1
Switching:
1-bit object for the transmission of switching telegrams (ON, OFF)
Scope of functions
•
Function of operating LED and of status LED parameterizable
•
Command on key-press parameterizable (ON, OFF)