11
4 Electrical connection
4.3 Suitable leads
LON interface
Screen
A screened twisted pair is recommended as a transmission line.
The screen must be connected to the technical earth (TE) of the LON interface.
Lead types
Other
connections
Standard stranded copper with 1.5 mm
2
max. cross-section
is suitable for
connecting transducers, the supply and the logic inputs to screw terminals.
Structure
Conductor cross-section
max. lead length
Line
1.4 mm
2
(16 AWG)
0.34mm
2
(22 AWG)
2700m
1400m
Ring/star/mixed
1.3 mm
2
(16 AWG)
0.34mm
2
(22 AWG)
500m
400m