22
8 Operation
8
Operation
8.1
Display and control elements
8.2
Troubleshooting
The device status is indicated by a multicolored LED (red/green/yellow).
(1)
Multicolored device status LED
LED signal
Device status (error message)
Status signal according to
NAMUR
Green (f = 1 Hz, t
on
/T = 0.9)
0 = normal operation
-
Red (f = 1 Hz, t
on
/T = 0.5)
1 = error
F
Yellow (f = 1 Hz, t
on
/T = 0.5)
2 = outside the specification
S
Red (f = 5 Hz, t
on
/T = 0.5)
4 = failure (serious error)
F
Yellow
Initialization phase
C
Error mes-
sage
Device func-
tion
Possible cause
Troubleshooting
0
All
No errors
-
2
Input for vol-
ume flow
Volume flow > MRE
Reduce the plant's volumetric flow
Use larger device nominal width
Partial filling/empty conduit
Fill pipe
Gas bubbles in the medium > level
1 (measurement still possible)
Bleed the system
Increase the system pressure
2
Analog output Burden too high
Check electrical connection
2
Digital output
Short circuit in output due to over-
load
Check electrical connection
4
General infor-
mation
Checksum of configuration data
faulty
Contact manufacturer
General error
4
Input for vol-
ume flow
Volume flow invalid
Contact manufacturer
Gas bubbles in the medium > level
2 (measurement no longer possi-
ble)