Technical data
1701649 • 2019/04
JUDO JPF-A
23
9
Technical data
Automatic backwash protective filter
JUDO PROFIMAT ¾" - 4"
JPF-A ¾" - 4"
The water to be filtered must be of drinking water quality.
Information
about:
JPF-A ¾"
JPF-A 1"
JPF-A 1¼" JPF-A 1½"
JPF-A 2"
Pipe connection
¾"
1"
1¼"
1½"
2"
Backwashing vol-
ume flow
1)
0,2-0,4 L/s
(3-6.5 gpm)
0,2-0,4 L/s
(3-6.5 gpm)
0,2-0,4 L/s
(3-6.5 gpm)
0,3-0,8 L/s
(5-13 gpm)
0,3-0,8 L/s
(5-13 gpm)
Backwashing time ca. 2 min
ca. 2 min
ca. 2 min
ca. 2 min
ca. 2 min
Nominal pressure
PN 16
PN 16
PN 16
PN 16
PN 16
Operating pressure
22-232 psi
(150-1600
kPa)
22-232 psi
(150-1600
kPa)
22-232 psi
(150-1600
kPa)
22-232 psi
(150-1600
kPa)
22-232 psi
(150-1600
kPa)
Rated flow after
backwashing
with 3 psi (20 kPa)
pressure loss
4.0 m³/h
(17.5 gpm)
4.5 m³/h
(20 gpm)
5.5 m³/h
(24 gpm)
16 m³/h
(70 gpm)
17 m³/h
(75 gpm)
Mesh size
2)
sieve insert
0.1 mm
0.1 mm
0.1 mm
0.1 mm
0.1 mm
Water temperature
and ambient tem-
perature
max. 30 °C
(86 °F)
max. 30 °C
(86 °F)
max. 30 °C
(86 °F)
max. 30 °C
(86 °F)
max. 30 °C
(86 °F)
Power connection
120 V AC / 60 Hz
Power consump-
tion operation
1 W
1 W
1 W
1 W
1 W
Power consump-
tion backwashing
max. 15 W max. 15 W max. 15 W max. 15 W
max. 15 W
Weight (version
AT)
4,2 kg
4,4 kg
4,9 kg
10,2 kg
11,5 kg
Weight (version
ATP)
4,9 kg
5,0 kg
5,6 kg
11,0 kg
12,0 kg
Order no.
8020218
8020219
8020268
8020269
8020270
1) Applies to a fully opened backwashing valve and 30 - 44 psi (200 - 300 kPa) mains
pressure.
2) Standard mesh size
100 µm
100 µm
100 µm
100 µm
100 µm
Summary of Contents for PROFIMAT JPF-A 1 1/2"
Page 28: ...Technical data 28 JUDO JPF A 1701649 2019 04 9 4 Circuit diagram for device control...
Page 30: ...Technical data 30 JUDO JPF A 1701649 2019 04 9 5 Spare parts JPF A 1...
Page 33: ...Technical data 1701649 2019 04 JUDO JPF A 33 JPF A 1 2...
Page 36: ...Technical data 36 JUDO JPF A 1701649 2019 04 JPF A 2 4...