JUDO FIMAT
19
Fault
6.
Fault
The opening of the units and the replace-
ment of the water pressure charged parts
may only be effected by authorized
personal in order the ensure the unit
security and its tightness.
The occurrence of a failure inside the device
will be indicated by the red control lamp.
Deleting the error message:
Disconnect the power supply from
the socket. Plug it back in after
approx. 5 seconds!
Help with faults:
Fault
Cause
Remedy
Permanent acoustic
signal sounding.
The DIP-switch was set
incorrectly.
Correct the position of the DIP-
switch! (see chapter “Setting the
backwashing interval”)
Red control lamp flashes
and acoustic signal
sounding.
Electrical or mechanical
failure.
–
Delete the error message!
–
Start backwashing again by
using the manual pushbutton!
If failure is occurring again:
Remove mains plug from the
socket.!
–
Inform the fitter or nearest
customer service centre!
–
Close ball valves!
All three control lamps
flash.
Services is necessary.
See chapter “Warranty and ser-
vices”!
Backwashing water
continues running.
Flushing valve not fully
closed.
–
Start backwashing again by
using the manual pushbutton!
Dirt in the flushing valve.
Water flow rate falls.
Screen is blocked.
Leaks in the filter.
–
Remove mains plug from the
socket!
–
Close ball valves!
–
Inform the fitter or nearest
customer service centre!
Filter cover becomes
turbid.
Filter hood has been
exposed to high tempera-
tures or solvents.
Hairline cracks on the
filter hood.
Summary of Contents for FIMAT JFXL-M 1 1/2