JUDO FIMAT
13
Operation
5.3
Differential pressure control
The selector shaft of the differential pres-
sure switch is set at the adjusting screw.
The value can be adjusted with a screw-
driver between 0.9 psi (6.2 kPa) and 9 psi
(62 kPa), see scale.
If the value is set too high, dirt may accumu-
late with low flow rate. During times of
higher water removal the differential pres-
sure will increase to an extent that damages
at the screen may occur.
5.4
Setting the backwashing
interval
ATTENTION
(see chapter “Safety information and
dangers due to non-compliance”)
–
Unwind the four screws of cover hood
and remove cover.
–
Set backwashing interval via contacts 3
to 6 of DIP-switches S1, see tab. 1.
–
Only one contact may be switched to the
left for adjustment.
–
When adjusted the wrong way, the
switch will react with an acoustic signal
(see chapter “Fault”).
–
Reattach cover and tighten it with the
four screws.
–
The backwash protective filter is ready
for operation after backwashing.
Fig. 7:
Differential pressure switch
Cable for electric circuit
Primary
pressure
Adjusting screw for differential
pressure adjustment
Outgoing
pressure
Disconnect the power supply from
the socket.
4
hour
8
hour
24
hour
1
week
1
month
Tab. 1: DIP switch S1
Ensure that the wastewater con-
nection functions before plugging
the power supply unit into the
socket.
Manual start of backwashing proce-
dure:
Push manual button. The backwash
time is set back.
1