JSP P5310 Manual Download Page 9

- 9 -

Low-Cost Programmable Transmitters P5310, P5311 with LHP Communication

Total measurement error on the analogue output of P5311:

Range 0 to 400 Ohm  ≤ ±0.15% SR or ≤ ±0.12 Ohm 
 

or corresponding temperature

Range 0 to 4000 Ohm ≤ ±0.15% SR or ≤ ±1.2 Ohm 
 

or corresponding temperature

Range -15 to 70 mV   ≤ ±0.15% SR or ≤ ±0.03 mV 
 

corresponding temperature

 

Range Pt100, Pt1000, Ni100, Ni1000

 

 

≤ ±0.15 % SR or ≤± 0.3 °C

 

Range Pt500 

≤ ±0.15 % SR or ≤± 0.6 °C

 

Range TC J, K, T, E, L  typ.  ≤± 0.15 % SR or 0.5 °C

 

Range TC R, S, B, C  typ. ≤± 0.15 % SR or 2 °C

 

(the greatest value is valid)

Characteristics:        

 

 

Linear with temperature or linear with input quantity, 

 

other upon request

Adjustability of the range:        
 

±1% to ±100% of the input range

Adjustability:
 

Inside the input range (the given measurement errors  

 

apply for suppression of the beginning ≤ 100% of the  

 

range)

Time constant (95 %):   
 

Adjustable 0.5 to 60 s (2 measurements per second)

Load resistance:  

R

L

 [Ohm] ≤ (U

N

 [V] - 9) / 0.022

Electric strength of galvanic isolation of P5311:
 

1000 VAC (test)

Isolation resistance of galvanic isolation of P5311:
 

Min. 100 M

Ohm

 

5.2 Supplementary parameters

Output current limitation:

Signal 3.8 to 20.5 mA acc. to NAMUR NE43
Limitation of error current to approx. 22 mA

Indication of sensor or transmitter error:
 

Optionally by current > 21 mA or < 3.6 mA

according to NAMUR NE43

Supply voltage effect: ≤ ±0.005 % / V
Influence of ambient temperature changes:  
 

Range 0 to 400 Ohm (≤ ±0.1% SR or ≤ ±0.08 Ohm 

 

or corresponding temperature) / 10 °C

 

Range 0 to 4000 Ohm (≤ ±0.1% SR or ≤ ±0.8 Ohm 

 

or corresponding temperature) / 10 °C

 

Range -15 to 70 mV (≤ ±0.1% SR or ≤ ±0.02 mV 

 

or corresponding temperature) / 10 °C 

 

(the greatest value is valid)

Long-term stability: 

 

 

≤ ±0.1 % of the preset range per 2 years

Electromagnetic compatibility:
 

Radiation and immunity acc. to EN 61326-1 

 

(Industrial environment)

MV ... measured value 
SR ... span of preset range

6. Tests, certificates and standards

6.1 Tests, certificates

Electromagnetic compatibility
Emission and immunity acc. to EN 61326-2-3
Intrinsically safe version (option EI1)
Certificate FTZÚ 06 ATEX 0353X + Supplements 1, 2 and 3
Version “n“ (version EN2)
Producer assessment ZV100006 (P5311) and ZV100011 
(P5310)

6.2 Standards

Transmitter is designed and manufactured according these
standards:
EN 61010-1

Version EI1:
EN 60079-0
EN 60079-11
EN 60079-26

Version EN2:
EN 60079-0
EN 60079-15

6.3 Marking and type tag information

Standard version:

Standard version:
P5311   

 

type number

Model:   

 

version

S/No: 

 

 

serial number

Czech Republic   

country of origin

 

 

 

logo of JSP, s.r.o.

www.jsp.cz 

 

contact for manufacturer

Tag of version EI1 includes further:

        

II 1G Ex ia IIC T4-T6 Ga

        

II 1D Ex ia IIIC T106°C Da

year of manufacture 
number of ATEX certificate

Tag of version EN2 includes further:

        II 3G Ex nA IIC T4 Gc
-40 °C ≤ Ta ≤ 85 °C
year of manufacture
document number of producer assessment report

6.4 Limiting conditions of use of a transmitter 
in an intrinsically safe version (code EI1)

Relation between the temperature class and ambient  
temperature:
 

T4 (T106 °C) 

-40 °C < T

amb

 < 85 °C

 

T5 (T76 °C)    

-40 °C < T

amb

 < 55 °C

 

T6 (T61 °C)   

-40 °C < T

amb

 < 40 °C

Summary of Contents for P5310

Page 1: ...www jsp sk This document applies to serial numbers 10090000 and higher One type of transmitter for all common resistance and thermocouple sensors Linearized output signal 4 to 20 mA Accuracy from 0 1...

Page 2: ...4 Installation operation and maintenance 4 1 Installation and commissioning 6 4 2 Description of setting and configuration using the communicator LHPWinCom 7 4 3 Description of setting and configurati...

Page 3: ...e cover and provided with an identification label with a mark of the output control The product must not be exposed to direct rain vibrations and shocks during transport 1 5 Storage The products shall...

Page 4: ...minal block temperature or by the entered constant temperature The inner sensor guarantees maximum accuracy and stability of cold junction temperature measurement If required compensation using an ext...

Page 5: ...5 Low Cost Programmable Transmitters P5310 P5311 with LHP Communication 3 3 Dimensional drawings Version P531x H1x Version P531x L1x 3 4 Block diagram...

Page 6: ...ctrostatic charging Such case may be a metal temperature sensor head or a suitable metal installation box if it does not contain magnesium nor titanium During installation it is also necessary to resp...

Page 7: ...the input quantity The fixed output mode can be closed by the program button or by disconnecting of the transmitter power supply Transmitters in version EI1 or EN2 Ex version can be set up using the c...

Page 8: ...0 to 400 C IEC 584 1 thermocouple B 100 to 1800 C IEC 584 1 thermocouple E 200 to 950 C IEC 584 1 thermocouple L 200 to 900 C DIN 43710 thermocouple C 0 to 2300 C N I S T Monograph 175 range can be se...

Page 9: ...esponding temperature 10 C Range 0 to 4000 Ohm 0 1 SR or 0 8 Ohm or corresponding temperature 10 C Range 15 to 70 mV 0 1 SR or 0 02 mV or corresponding temperature 10 C the greatest value is valid Lon...

Page 10: ...RTMod Miniature HART modem with galvanic isolation USB RS232C Communication interface for to USB port of the PC PT1000A Compensation resistor Pt1000 30 to 150 C for external compensation of thermocoup...

Page 11: ...JSP Industrial Controls JSP s r o Raisova 547 506 01 Ji n Czech Republic 420 493 760 811 export jsp cz www jsp cz Your Supplier...

Reviews: