JSP P5310 Manual Download Page 6

- 6 -

Low-Cost Programmable Transmitters P5310, P5311 with LHP Communication

4. Installation, operation and maintenance
4.1 Installation and commissioning

4.1.1 General

After  mounting  and  correct  connection,  switch  on  the  power 
supply.
During  the  installation  of  transmitters  in  environment  with 
higher level of interference, protection of transmitters against 
interference and induced overvoltage must be ensured.
According  to  the  standard  engineering  practice,  it  is 
recommended  to  separate  signal  and  power  wires  into 
separate gutters and use shielded signal cables with twisted 
wires.  In  case  of  outdoor  wires,  it  is  necessary  to  solve  the 
overvoltage  protection  of  the  transmitter  as  a  part  of  overall 
solution of protecting system from the effects of atmospheric 
electricity.

4.1.2 Special conditions for use of intrinsically safe 
version (code EI1)  
        II 1G Ex ia IIC T4-T6 Ga 
        II 1D Ex ia IIIC T106°C Da

When installed in 

explosive environment of 

gasses or 

vapours

,

  the  transmitter  shall  be  installed  in  a  metal 

case with protection at least IP 20 to avoid electrostatic 

charging.  Such  case  may  be  a  metal  temperature  sensor 
head or a suitable metal installation box if it does not contain 
aluminium, magnesium, titanium nor zircon. During installation 
it  is  also  necessary  to  respect  other  safety  standards.  The 
transmitter may be connected on its input and output sides only 
to suitable certified associated apparatus or simple apparatus 
in the sense of the standard EN 60079-11 with respecting of 
the limiting conditions. The transmitter may be installed in an 
environment  with  explosion  hazard  Zone  0,  Zone  1  or  Zone 
2 only if all the related conditions are fulfilled. The equipment 
provides  the  necessary  level  of  protection  during  normal 
operation and with one or two faults.

When  installed  in 

explosive  environment  of 

dusts

,

  the 

transmitter  shall  be  installed  in  a  metal  case  to  avoid 
electrostatic charging. Such case may be a metal temperature 
sensor head or a suitable metal installation box if it does not 
contain magnesium nor titanium. During installation it is also 
necessary  to  respect  other  safety  standards. The  transmitter 
may be connected on its input and output sides only to suitable 
certified associated apparatus or simple apparatus in the sense 
of  the  standard  EN  60241-11  with  respecting  of  the  limiting 
conditions. The transmitter may be installed in an environment 
with explosion hazard Zone 20, Zone 21 or Zone 22 only if all 
the related conditions are fulfilled. The equipment provides the 
necessary level of protection during normal operation and with 
one or two faults.
Galvanic  isolation  of  input  and  output  electrical  circuit  is  not 
faulty free isolation in terms of Intrinsically safety and it should 
be taken into account during the safety analysis of the system.

4.1.3 Special conditions for using of a transmitter in 
version (code EN2)

       

II 3G Ex nA IIC T4 Gc

The transmitter shall be installed in a metal case with 
outlets  and  protection  at  least  IP  54  (category  1  acc. 
to  EN  60529)  that  meets  requirement  of  mechanical 

resistance acc. to the standards EN 60079-0 and EN 60079-
15.  Such  case  may  be  for  example  the  metal  temperature 
sensor  head  with  protection  IP  54  or  a  suitable  installation. 
During installation it is also necessary to respect other safety 
standards.  Output  and  supply  circuits  or  the  transmitter  can 
be  connected  only  when  no  voltage  is  present!  In  case  the 
temperature in place of the cable input is higher than 70 °C, 
a suitable cable and bushing shall be used and temperature acc. 
to par. 16.6 of the standard EN 60079-0 and must be marked 
on the outer side of the case! The transmitter may be installed 
in an hazardous areas in Zone 2. The equipment provides the 
necessary level of protection during normal operation. 

4.1.4 Electrical connection

Version P531x H1x

4w

3w

4w

4w

RTD

TC

PO T

TC

RTD

NAPÁJECÍ

ZDRO J

LHP komunikátor

mA

TEST

R

i

 

R

L

250 Ohm

15 Ohm

(pro komunikaci)

mA

VÝSTUP

~

POWER 

SUPPLY

LHP 

Communicator

(for communication)

OUTPUT

Summary of Contents for P5310

Page 1: ...www jsp sk This document applies to serial numbers 10090000 and higher One type of transmitter for all common resistance and thermocouple sensors Linearized output signal 4 to 20 mA Accuracy from 0 1...

Page 2: ...4 Installation operation and maintenance 4 1 Installation and commissioning 6 4 2 Description of setting and configuration using the communicator LHPWinCom 7 4 3 Description of setting and configurati...

Page 3: ...e cover and provided with an identification label with a mark of the output control The product must not be exposed to direct rain vibrations and shocks during transport 1 5 Storage The products shall...

Page 4: ...minal block temperature or by the entered constant temperature The inner sensor guarantees maximum accuracy and stability of cold junction temperature measurement If required compensation using an ext...

Page 5: ...5 Low Cost Programmable Transmitters P5310 P5311 with LHP Communication 3 3 Dimensional drawings Version P531x H1x Version P531x L1x 3 4 Block diagram...

Page 6: ...ctrostatic charging Such case may be a metal temperature sensor head or a suitable metal installation box if it does not contain magnesium nor titanium During installation it is also necessary to resp...

Page 7: ...the input quantity The fixed output mode can be closed by the program button or by disconnecting of the transmitter power supply Transmitters in version EI1 or EN2 Ex version can be set up using the c...

Page 8: ...0 to 400 C IEC 584 1 thermocouple B 100 to 1800 C IEC 584 1 thermocouple E 200 to 950 C IEC 584 1 thermocouple L 200 to 900 C DIN 43710 thermocouple C 0 to 2300 C N I S T Monograph 175 range can be se...

Page 9: ...esponding temperature 10 C Range 0 to 4000 Ohm 0 1 SR or 0 8 Ohm or corresponding temperature 10 C Range 15 to 70 mV 0 1 SR or 0 02 mV or corresponding temperature 10 C the greatest value is valid Lon...

Page 10: ...RTMod Miniature HART modem with galvanic isolation USB RS232C Communication interface for to USB port of the PC PT1000A Compensation resistor Pt1000 30 to 150 C for external compensation of thermocoup...

Page 11: ...JSP Industrial Controls JSP s r o Raisova 547 506 01 Ji n Czech Republic 420 493 760 811 export jsp cz www jsp cz Your Supplier...

Reviews: