INSTALLATION

IF THIS SOLID FUEL ROOM HEATER IS NOT

PROPERLY INSTALLED A HOUSE FIRE MAY

RESULT.  FOR YOUR SAFETY, FOLLOW THE

INSTALLATION  DIRECTIONS.    CONTACT

THE LOCAL BUILDING OR FIRE OFFICIALS

ABOUT 

RESTRICTIONS 

AND

INSTALLATION 

INSPECTION

REQUIREMENTS IN YOUR AREA.

TOP OR REAR EXIT FLUE

The  Oslo  F500    is  shipped  with  the  flue  collar,

gasketing and hardware inside the stove.  To install

the flue collar in the top or rear exit position remove

the tape from the gasketing and adhere to the groove

on the back of the stove around the flue opening.

Place the flue collar on the stove in the top or rear

exit position and secure with the nut, bolt and washer.

The nut and washer are placed on the inside of the

stove.

STOVE  PIPE

CHIMNEY  CONNECTOR

The chimney connector is a single walled pipe used

to connect the stove to the chimney.  For use with

the OSLO F500 the chimney connector MUST be

6” in diameter, with a minimum thickness of 24 gauge

black steel.

Aluminum and Galvanized steel pipe is not acceptable

for  use  with  the  OSLO  F500.      These  materials

cannot  withstand  the  extreme  temperatures  of  a

wood fire and can give off toxic fumes when heated.

Do not use the connector pipe as a chimney.

For the best performance the chimney connector

should be as short and direct as possible, with no

more than two 90

°

 elbows.  The maximum horizontal

run is 36” and a recommended total length of stove

pipe  should  not  exceed  10  feet.      Always  slope

horizontal  runs  upward  ¼”  per  foot  toward  the

chimney.

No part of the chimney connector may pass through

an  attic  or  roof  space,  closet  or  other  concealed

space, or through a floor or ceiling.  All sections of

the  chimney  connectors  must  be  accessible  for

cleaning.  Where passage through a wall or partition

of combustible construction is desired, the installation

must conform with NFPA 211 or CAN/CSA-B365,

and is also addressed in this manual.

DO  NOT  CONNECT  THIS  UNIT  TO  A

CHIMNEY  FLUE  SERVICING ANOTHER

APPLIANCE.

Reminder:

Your  local  officials  have  final  authority  in

determining  if  a  proposed  installation  is

acceptable.  Any requirement, that is requested

by the local authority having jurisdiction, that is

not  specifically  addressed  in  THIS  manual,

defaults to NFPA 211, and local codes in the

U.S. or in Canada, CAN/CSA-B365-M and local

codes.

Each chimney connector or stove pipe section must

be installed to the stove flue collar and to each other

with the male (crimped) end toward the stove.  

See

figure 1.

This prevents any amount of condensed or liquid

creosote from running down the outside of the pipe

or the stove top.  All joints, including the flue collar

connection must be secured with three sheet metal

screws to ensure that the sections do not separate.

4

FIGURE 1

DO NOT CONNECT THIS STOVE TO ANY

AIR DISTRIBUTION DUCT OR SYSTEM.

Summary of Contents for Oslo F 500

Page 1: ...instructions for future reference Avis de s curit Une installation non appropri e de ce po le de chauffage risque de provoquer un incendie Assurez votre s curit en respectant les directives d installa...

Page 2: ...tallations 10 Mobile Home Installations 10 Operation 13 Controls 13 Breaking in your Stove 13 Starting Maintaining 14 Formation of Creosote 14 Maintenance 15 Ash Removal 15 Glass Care 15 General Maint...

Page 3: ...lways consult your local building inspector or authority having jurisdiction to determine what regulations apply in your area NOTICES BE SURE TO READ THIS ENTIRE MANUAL BEFORE YOU INSTALL OR USE YOUR...

Page 4: ...h no more than two 90 elbows The maximum horizontal run is 36 and a recommended total length of stove pipe should not exceed 10 feet Always slope horizontal runs upward per foot toward the chimney No...

Page 5: ...of the chimney 5 CHIMNEY REQUIREMENTS There are two types of chimneys suitable for the OSLO F500 1 A code approved masonry chimney with a flue liner 2 A prefabricated chimney complying with the requir...

Page 6: ...rick with a minimum of 3 thick 4 nominal Refractory mortar must be used at the junction of the chimney and the pass through liner The pass through liner must not penetrate the chimney liner beyond the...

Page 7: ...nspector authorized J tul Dealer NFPA 211 in the U S or CAN CSA B635 in Canada for other approved wall pass through methods CONNECTING TO THE CHIMNEY Masonry Chimney When installing a OSLO F500 into a...

Page 8: ...ust be installed to resize the flue A new sheet metal damper block off plate must be installed around the connector pipe at the damper frame and sealed with the proper sealant usually High Temp Silico...

Page 9: ...can burn i e sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are visible and also include materials that are behind non combustible materials If you are not sure o...

Page 10: ...ceiling height off the top of the stove in a protected ceiling installation is 15 380mm 7 ALCOVE floor protection must be a UL ULC or WHI listed hearth pad or a non combustible materialwithaminimumRv...

Page 11: ...PARALLEL TO THE WALL UNPROTECTED SURFACE CORNER INSTALLATION PROTECTED SURFACE PER NFPA 211 CORNER INSTALLATION IMPORTANT CONNECTOR HEATSHIELDS AND DOUBLE WALL PIPE MUST BE A LISTEDPRODUCT ALWAYS FOLL...

Page 12: ...PROTECTED SURFACE NFPA 211 CLEARANCES pipe VERTICAL INSTALLATION VERTICAL INATALLATION Single wall 18 12 with no heatshields 460mm 300mm Single wall 6 6 with connector shields 150mm 150mm Double wall...

Page 13: ...Breaking in your new stove Your new OSLO F500 is constructed of cast iron and stove furnace cement This type of construction requires the stove to be broken in gradually so that heat expansion does n...

Page 14: ...FYOUNOTICETHISCONDITION Adding Fuel When reloading the stove while it is still hot and a bed of hot embers still exist follow this reloading procedure Always wear gloves when tending to the stove Push...

Page 15: ...roper cleaning procedure is as follows 1 Glass needs to be COMPLETELY COOL 2 Only use a cleaner that is specifically designed for this purpose The use of abrasives will damage the glass and ultimately...

Page 16: ...been approved for use as an open fireplace with front door open This feature is especially nice when the ambience of a fire is desired Some care should be taken when operating the stove as a fireplac...

Page 17: ...Heatshield part 154332 A stove rear heatshield has been specifically designed for the OSLO F500 to reduce clearances off the rear of the stove to combustible materials Use of the heatshield DOES NOT a...

Page 18: ...ED VIEW OF THE OSLO F500 ONLY USE REPLACEMENTS PARTS PROVIDED THROUGH YOUR AUTHORIZED J TUL DEALER 18 19 18 17 14 16 15 20 22 23 24 21 25 26 27 28 29 34 30 31 33 32 29 1 2 3 4 5 6 7 8 9 10 11 12 13 41...

Page 19: ...f C 1 25 therefore R brick 1 C 1 1 25 0 80 1 8 mineral board of k 0 29 therefore R mineral board 1 29 X 0 125 0 431 Total R R brick R mineral board 0 8 0 431 1 231 Step C Compare proposed system R 1 2...

Page 20: ...ue a policy of constant product development Products supplied may therefore differ in specification colour and type of accessories from those illustrated and described in the brochure J tul vise sans...

Reviews: