background image

Prefabricated Chimneys

If a prefabricated metal chimney is to be used it

must be a chimney type that is tested and listed for

use  with  solid  fuel  burning  appliances.    High

Temperature (HT) Chimney Standard UL 103 for

the U.S. and High Temperature Standard  ULC

S-629 for Canada.

Masonry  Chimneys

When installing the OSLO F500 into a masonry

chimney you must conform to all of the following

guidelines:

·

The masonry chimney must have a fireclay liner

or equivalent,  with a minimum thickness of

5/8” and must be installed with refractory mortar.

There must be at least ½” air space between

the flue liner and chimney wall.

·

The fireclay flue liner must have a nominal size

of 8” X 8”, and should not be larger than

8”X 12”.  If a round fireclay liner is to be used it

must have a minimum inside diameter of 6” and

not larger than 8” in diameter. If a chimney with

larger dimensions is to be used, it should be

relined with an appropriate liner that is code

approved.

·

The masonry wall of the chimney, if brick or

modular block, must be a minimum of 4” nominal

thickness.  A mountain or rubble stone wall must

be at least 12” thick.

·

A newly-built chimney must conform to local

codes  and  in  their  absence  must  recognize

national regulations.

·

When  using  an  existing  chimney,  it  must  be

inspected by a professional licensed chimney

sweep, fire official, or code officer, to ensure

that the chimney is in proper working order.

·

No other appliance can be vented into the same

flue.

·

An airtight clean-out door should be located at

the base of the chimney.

5

CHIMNEY  REQUIREMENTS

There are two types of chimneys suitable for the

 OSLO F500:

1.   A code- approved masonry chimney with a flue

      liner.

2.   A prefabricated chimney complying with the

      requirements for Type HT (2100

°

F) chimneys

      per UL 103 or ULC S629.

The chimney size should not be less than the cross-

sectional area of the flue collar, and not more than

three times greater than the cross-sectional area of

the flue collar.

When selecting a chimney type and the location for

the chimney in the house, keep this in mind:  it is the

chimney that makes the stove work, NOT the stove

that makes the chimney work.  This is because a

chimney actually creates a suction, called “draft”

which pulls air through the stove.

Several factors affect draft:  chimney height, cross-

sectional area (size), and temperature of the chimney,

as  well  as  the  proximity  of  surrounding  trees  or

buildings.

As a result, a short masonry chimney on the exterior

of a house will give the poorest performance.  This

is  because  it  can  be  very  difficult  to  warm  the

chimney  thereby  creating  inadequate  draft.    In

extremely cold northern areas it may be necessary

to reline the chimney or extend its height to help

establish draft.

Oppositely, a tall masonry chimney inside the house

is easier to keep warm and will perform the best.

The following guidelines give the necessary chimney

requirements based on the national code (ANSI-

NFPA  211for  the  US. And  CSA  CAN-B365  for

Canada).  However, many local codes differ from

the  national  code  to  take  into  account  climate,

altitude, or other factors.  It is important that you

check with your local building officials to find out

what codes apply in your area before installing your

new OSLO F500.

Summary of Contents for Oslo F 500

Page 1: ...instructions for future reference Avis de s curit Une installation non appropri e de ce po le de chauffage risque de provoquer un incendie Assurez votre s curit en respectant les directives d installa...

Page 2: ...tallations 10 Mobile Home Installations 10 Operation 13 Controls 13 Breaking in your Stove 13 Starting Maintaining 14 Formation of Creosote 14 Maintenance 15 Ash Removal 15 Glass Care 15 General Maint...

Page 3: ...lways consult your local building inspector or authority having jurisdiction to determine what regulations apply in your area NOTICES BE SURE TO READ THIS ENTIRE MANUAL BEFORE YOU INSTALL OR USE YOUR...

Page 4: ...h no more than two 90 elbows The maximum horizontal run is 36 and a recommended total length of stove pipe should not exceed 10 feet Always slope horizontal runs upward per foot toward the chimney No...

Page 5: ...of the chimney 5 CHIMNEY REQUIREMENTS There are two types of chimneys suitable for the OSLO F500 1 A code approved masonry chimney with a flue liner 2 A prefabricated chimney complying with the requir...

Page 6: ...rick with a minimum of 3 thick 4 nominal Refractory mortar must be used at the junction of the chimney and the pass through liner The pass through liner must not penetrate the chimney liner beyond the...

Page 7: ...nspector authorized J tul Dealer NFPA 211 in the U S or CAN CSA B635 in Canada for other approved wall pass through methods CONNECTING TO THE CHIMNEY Masonry Chimney When installing a OSLO F500 into a...

Page 8: ...ust be installed to resize the flue A new sheet metal damper block off plate must be installed around the connector pipe at the damper frame and sealed with the proper sealant usually High Temp Silico...

Page 9: ...can burn i e sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are visible and also include materials that are behind non combustible materials If you are not sure o...

Page 10: ...ceiling height off the top of the stove in a protected ceiling installation is 15 380mm 7 ALCOVE floor protection must be a UL ULC or WHI listed hearth pad or a non combustible materialwithaminimumRv...

Page 11: ...PARALLEL TO THE WALL UNPROTECTED SURFACE CORNER INSTALLATION PROTECTED SURFACE PER NFPA 211 CORNER INSTALLATION IMPORTANT CONNECTOR HEATSHIELDS AND DOUBLE WALL PIPE MUST BE A LISTEDPRODUCT ALWAYS FOLL...

Page 12: ...PROTECTED SURFACE NFPA 211 CLEARANCES pipe VERTICAL INSTALLATION VERTICAL INATALLATION Single wall 18 12 with no heatshields 460mm 300mm Single wall 6 6 with connector shields 150mm 150mm Double wall...

Page 13: ...Breaking in your new stove Your new OSLO F500 is constructed of cast iron and stove furnace cement This type of construction requires the stove to be broken in gradually so that heat expansion does n...

Page 14: ...FYOUNOTICETHISCONDITION Adding Fuel When reloading the stove while it is still hot and a bed of hot embers still exist follow this reloading procedure Always wear gloves when tending to the stove Push...

Page 15: ...roper cleaning procedure is as follows 1 Glass needs to be COMPLETELY COOL 2 Only use a cleaner that is specifically designed for this purpose The use of abrasives will damage the glass and ultimately...

Page 16: ...been approved for use as an open fireplace with front door open This feature is especially nice when the ambience of a fire is desired Some care should be taken when operating the stove as a fireplac...

Page 17: ...Heatshield part 154332 A stove rear heatshield has been specifically designed for the OSLO F500 to reduce clearances off the rear of the stove to combustible materials Use of the heatshield DOES NOT a...

Page 18: ...ED VIEW OF THE OSLO F500 ONLY USE REPLACEMENTS PARTS PROVIDED THROUGH YOUR AUTHORIZED J TUL DEALER 18 19 18 17 14 16 15 20 22 23 24 21 25 26 27 28 29 34 30 31 33 32 29 1 2 3 4 5 6 7 8 9 10 11 12 13 41...

Page 19: ...f C 1 25 therefore R brick 1 C 1 1 25 0 80 1 8 mineral board of k 0 29 therefore R mineral board 1 29 X 0 125 0 431 Total R R brick R mineral board 0 8 0 431 1 231 Step C Compare proposed system R 1 2...

Page 20: ...ue a policy of constant product development Products supplied may therefore differ in specification colour and type of accessories from those illustrated and described in the brochure J tul vise sans...

Reviews: