UNPROTECTED SURFACE
PROTECTED SURFACE NFPA 211
STOVE CLEARANCES
PARALLEL INSTALLATION
PARALLEL INSTALLATION
SIDE
REAR
CORNER* SIDE
REAR
CORNER*
Stove-no heatshield
14"
A
18"
B
13"
C
6"
D
12"
E
9"
F
Single wall pipe
355mm
460mm
330mm
150mm
300mm
230mm
Stove-with rear heatshield
14"
G
10"
H
9"
I
6"
J
10
K
9"
L
Single wall pipe
355mm
255mm
230mm
150mm
255mm
230mm
Stove-with rear heatshield
14"
M
6"
N
9"
O
6"
P
6"
Q
6"
R
with connector shield
355mm
150mm
230mm
150mm
150mm
150mm
Stove-rear heatshield
14"
S
6"
T
9"
U
6"
V
6"
W
6"
X
with double wall pipe
355mm
150mm
230mm
150mm
150mm
150mm
CONNECTOR
UNPROTECTED SURFACE
PROTECTED SURFACE NFPA 211
CLEARANCES (pipe)
VERTICAL INSTALLATION
VERTICAL INATALLATION
Single wall
18"
12"
with no heatshields
460mm
300mm
Single wall
6"
6"
with connector shields
150mm
150mm
Double wall pipe
6"
6"
150mm
150mm
UNPROTECTED SURFACE
PROTECTED SURFACE NFPA 211
HORIZONTAL INSTALLATION
HORIZONTAL INSTALLATION
Single wall connector
18" 460mm
12" 300mm
Double wall Pipe
6" 150mm
6" 150mm
MANTEL AND TRIM
Stove to 1" thick or less,
side trim
12" 300mm
CLEARANCES
Stove to 1" thick or less,
top trim
16" 410mm
Stove to
mantel
- maximum mantel depth 12"
30" 765mm
* ATTENTION: STOVE AND PIPE CLEARANCES MUST BOTH BE TAKEN INTO CONSIDERATION.
THE GREATER CLEARANCE DICTATES THE STOVES POSITION.
* USE OF THE LEFT SIDE LOAD DOOR IS PROHIBITED IN ALCOVE AND CORNER
INSTALLATIONS.
12
OSLO F500 WOODSTOVE CLEARANCES