background image

ALTERNATE  FLOOR  PROTECTION

All  floor  protection  materials  must  be  non-combustible  ie.  metal,

brick,  stone,  mineral  fiber  boards).    Any  combustible  material

may not be used.

The  easiest  means  of  determining  if  a  proposed  alternate  floor

material  meets  requirements  listed  in  this  manual  is  to  follow  this

procedure.

R-value  =  thermal  resistance

k-value  =  thermal  conductivity

C-value  =  thermal  conductance

1.    Convert  the  specification  to  R-value;

a.  If  R-value  is  given,  no  conversion  is

needed.

b. If k-value is given with a required

thickness  (T)  in  inches:  R=1/k  X T.

c. If C-value is given: R=1/C.

2.    Determine  the  R-value  of  the  proposed  alternate

          floor  protector.

a.  Use  the  formula  in  Step  1  to  convert

values  not  expressed  as  “R”.

b. For multiple layers, add R-values of each

layer  to  determine  overall  R-value.

3.    If  the  overall  R-value  of  the  sustem  is  greater

          than  the  R-value  of  the  specified  floor  protector,

     the alternate is acceptable.

EXAMPLE:

The  specified  floor  protector  should  be  3/4”  thick  material  with  a

k-factor  of  0.84.    The  proposed  alternate  is  4”  brick  with  a  C-

factor  of  1.25  over

1/8”  mineral  board  witha  k-factor  of  0.29.

Step  A.    Use  formula  above  to  convert  specifications  to  R-value.

R=1/k X T= 1/.84 X .75 = .893

Step B.  Calculate R of proposed system.

4”  brick  of  C-1.25,  therefore

R brick = 1/C = 1/1.25 = 0.80.

1/8”  mineral  board  of  k  =  0.29  therefore

R mineral board = 1/.29 X 0.125 = 0.431

Total R = R brick + R mineral board=

0.8  +  0.431=

1.231

Step C.  Compare proposed system R = 1.231 to specified R of

0.893.  Since R is  greater  than  required,  the  system  is acceptable.

Definitions:

Thermal  conductance  =

C =        Btu        =           W

                      (hr)(ft

2

)(F)          (m

2

)(K)

Thermal  conductivity  =

            

k =

     Btu        =           W        =     (Btu)

                  (hr)(ft

2

)(F)          (m

2

)(K)       (hr)(ft)(F)

Thermal  resistance  =

R = 

     Btu        =       (m

2

)(K)      =     (Btu)(inch)

                     (hr)(ft

2

)(F)               W                  (hr)(ft

2

)(F)

FOR  THE  JØTUL  OSLO  F500    WOOD  STOVE  REQUIRES

FLOOR  PROTECTION  WITH A 

MINIMUM  INSULATING  R

VALUE  OF 0.5.

ALCOVE INSTALLATION REQUIRE A MINIMUM R VALUE

OF 1.6. (IF A UL/ULC or WHI LISTED HEARTH PAD IS NOT

USED.)

APPENDIX A:

19

PARTS LIST FOR THE OSLO F500

1

ash door

2

ash lip

3

front door

4

front

5

right side

6

left side

7

side door

8

rear plate

9

top

10

top cover

11

bottom

12

leg

13

smoke outlet

14

ash  house

15

ashpan

16

inner bottom

17

firegrate

18

refractory brick

19

air manifold

20

tube frame holder

21

bottom left tube holder

22

upper left tube holder

23

front tube

23

middle tube

24

rear tube

25

bottom right tube holder

26

upper right tube holder

27

top burn plate

28

insulating blanket (top)

*

gasketing for top

*

gasketing for top cover

29

side burn plates 2 pcs

*

insulating blanket for sides

30

door glass

*

glass  gasketing

*

glass clips

31

inner front

32

primary air lever

33

air valve/slider

34

inspection cover

optional equipment

40

bottom heatshield

41

rear heatshield

42

top exit shield

Summary of Contents for Oslo F 500

Page 1: ...instructions for future reference Avis de s curit Une installation non appropri e de ce po le de chauffage risque de provoquer un incendie Assurez votre s curit en respectant les directives d installa...

Page 2: ...tallations 10 Mobile Home Installations 10 Operation 13 Controls 13 Breaking in your Stove 13 Starting Maintaining 14 Formation of Creosote 14 Maintenance 15 Ash Removal 15 Glass Care 15 General Maint...

Page 3: ...lways consult your local building inspector or authority having jurisdiction to determine what regulations apply in your area NOTICES BE SURE TO READ THIS ENTIRE MANUAL BEFORE YOU INSTALL OR USE YOUR...

Page 4: ...h no more than two 90 elbows The maximum horizontal run is 36 and a recommended total length of stove pipe should not exceed 10 feet Always slope horizontal runs upward per foot toward the chimney No...

Page 5: ...of the chimney 5 CHIMNEY REQUIREMENTS There are two types of chimneys suitable for the OSLO F500 1 A code approved masonry chimney with a flue liner 2 A prefabricated chimney complying with the requir...

Page 6: ...rick with a minimum of 3 thick 4 nominal Refractory mortar must be used at the junction of the chimney and the pass through liner The pass through liner must not penetrate the chimney liner beyond the...

Page 7: ...nspector authorized J tul Dealer NFPA 211 in the U S or CAN CSA B635 in Canada for other approved wall pass through methods CONNECTING TO THE CHIMNEY Masonry Chimney When installing a OSLO F500 into a...

Page 8: ...ust be installed to resize the flue A new sheet metal damper block off plate must be installed around the connector pipe at the damper frame and sealed with the proper sealant usually High Temp Silico...

Page 9: ...can burn i e sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are visible and also include materials that are behind non combustible materials If you are not sure o...

Page 10: ...ceiling height off the top of the stove in a protected ceiling installation is 15 380mm 7 ALCOVE floor protection must be a UL ULC or WHI listed hearth pad or a non combustible materialwithaminimumRv...

Page 11: ...PARALLEL TO THE WALL UNPROTECTED SURFACE CORNER INSTALLATION PROTECTED SURFACE PER NFPA 211 CORNER INSTALLATION IMPORTANT CONNECTOR HEATSHIELDS AND DOUBLE WALL PIPE MUST BE A LISTEDPRODUCT ALWAYS FOLL...

Page 12: ...PROTECTED SURFACE NFPA 211 CLEARANCES pipe VERTICAL INSTALLATION VERTICAL INATALLATION Single wall 18 12 with no heatshields 460mm 300mm Single wall 6 6 with connector shields 150mm 150mm Double wall...

Page 13: ...Breaking in your new stove Your new OSLO F500 is constructed of cast iron and stove furnace cement This type of construction requires the stove to be broken in gradually so that heat expansion does n...

Page 14: ...FYOUNOTICETHISCONDITION Adding Fuel When reloading the stove while it is still hot and a bed of hot embers still exist follow this reloading procedure Always wear gloves when tending to the stove Push...

Page 15: ...roper cleaning procedure is as follows 1 Glass needs to be COMPLETELY COOL 2 Only use a cleaner that is specifically designed for this purpose The use of abrasives will damage the glass and ultimately...

Page 16: ...been approved for use as an open fireplace with front door open This feature is especially nice when the ambience of a fire is desired Some care should be taken when operating the stove as a fireplac...

Page 17: ...Heatshield part 154332 A stove rear heatshield has been specifically designed for the OSLO F500 to reduce clearances off the rear of the stove to combustible materials Use of the heatshield DOES NOT a...

Page 18: ...ED VIEW OF THE OSLO F500 ONLY USE REPLACEMENTS PARTS PROVIDED THROUGH YOUR AUTHORIZED J TUL DEALER 18 19 18 17 14 16 15 20 22 23 24 21 25 26 27 28 29 34 30 31 33 32 29 1 2 3 4 5 6 7 8 9 10 11 12 13 41...

Page 19: ...f C 1 25 therefore R brick 1 C 1 1 25 0 80 1 8 mineral board of k 0 29 therefore R mineral board 1 29 X 0 125 0 431 Total R R brick R mineral board 0 8 0 431 1 231 Step C Compare proposed system R 1 2...

Page 20: ...ue a policy of constant product development Products supplied may therefore differ in specification colour and type of accessories from those illustrated and described in the brochure J tul vise sans...

Reviews: