Installation and Operating Instructions for USA

Installation et fonctionnement pour Canada

Safety notice:

 If this solid fuel room heater is not properly installed, a house fire may result. For

your safety, follow the installation directions. Contact local building or fire officials about restrictions

and installation inspection requirements in your area. Kindly save  these instructions for future

reference.

Avis de sécurité: 

Une installation non appropriée de ce poêle de chauffage risque de provoquer un

incendie. Assurez votre sécurité en respectant les directives d’installation suivantes. Consultez les

autorités locales du bâtiment ou de la prévention des incendies au sujet des restrictions et exigences

relatives aux inspections d’installations dans votre région.

Tested and listed by ITS Intertek Testing Services,  Middleton, Wisconsin.

Tested to U.S. Standards: ANSI/UL 1482, Canadian Standards: CAN/ULC-S627-M93

. . . . . . . . . . . . . . . . . . . .

Jotul F 500

Oslo Woodstove

Summary of Contents for Oslo F 500

Page 1: ...instructions for future reference Avis de s curit Une installation non appropri e de ce po le de chauffage risque de provoquer un incendie Assurez votre s curit en respectant les directives d installa...

Page 2: ...tallations 10 Mobile Home Installations 10 Operation 13 Controls 13 Breaking in your Stove 13 Starting Maintaining 14 Formation of Creosote 14 Maintenance 15 Ash Removal 15 Glass Care 15 General Maint...

Page 3: ...lways consult your local building inspector or authority having jurisdiction to determine what regulations apply in your area NOTICES BE SURE TO READ THIS ENTIRE MANUAL BEFORE YOU INSTALL OR USE YOUR...

Page 4: ...h no more than two 90 elbows The maximum horizontal run is 36 and a recommended total length of stove pipe should not exceed 10 feet Always slope horizontal runs upward per foot toward the chimney No...

Page 5: ...of the chimney 5 CHIMNEY REQUIREMENTS There are two types of chimneys suitable for the OSLO F500 1 A code approved masonry chimney with a flue liner 2 A prefabricated chimney complying with the requir...

Page 6: ...rick with a minimum of 3 thick 4 nominal Refractory mortar must be used at the junction of the chimney and the pass through liner The pass through liner must not penetrate the chimney liner beyond the...

Page 7: ...nspector authorized J tul Dealer NFPA 211 in the U S or CAN CSA B635 in Canada for other approved wall pass through methods CONNECTING TO THE CHIMNEY Masonry Chimney When installing a OSLO F500 into a...

Page 8: ...ust be installed to resize the flue A new sheet metal damper block off plate must be installed around the connector pipe at the damper frame and sealed with the proper sealant usually High Temp Silico...

Page 9: ...can burn i e sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are visible and also include materials that are behind non combustible materials If you are not sure o...

Page 10: ...ceiling height off the top of the stove in a protected ceiling installation is 15 380mm 7 ALCOVE floor protection must be a UL ULC or WHI listed hearth pad or a non combustible materialwithaminimumRv...

Page 11: ...PARALLEL TO THE WALL UNPROTECTED SURFACE CORNER INSTALLATION PROTECTED SURFACE PER NFPA 211 CORNER INSTALLATION IMPORTANT CONNECTOR HEATSHIELDS AND DOUBLE WALL PIPE MUST BE A LISTEDPRODUCT ALWAYS FOLL...

Page 12: ...PROTECTED SURFACE NFPA 211 CLEARANCES pipe VERTICAL INSTALLATION VERTICAL INATALLATION Single wall 18 12 with no heatshields 460mm 300mm Single wall 6 6 with connector shields 150mm 150mm Double wall...

Page 13: ...Breaking in your new stove Your new OSLO F500 is constructed of cast iron and stove furnace cement This type of construction requires the stove to be broken in gradually so that heat expansion does n...

Page 14: ...FYOUNOTICETHISCONDITION Adding Fuel When reloading the stove while it is still hot and a bed of hot embers still exist follow this reloading procedure Always wear gloves when tending to the stove Push...

Page 15: ...roper cleaning procedure is as follows 1 Glass needs to be COMPLETELY COOL 2 Only use a cleaner that is specifically designed for this purpose The use of abrasives will damage the glass and ultimately...

Page 16: ...been approved for use as an open fireplace with front door open This feature is especially nice when the ambience of a fire is desired Some care should be taken when operating the stove as a fireplac...

Page 17: ...Heatshield part 154332 A stove rear heatshield has been specifically designed for the OSLO F500 to reduce clearances off the rear of the stove to combustible materials Use of the heatshield DOES NOT a...

Page 18: ...ED VIEW OF THE OSLO F500 ONLY USE REPLACEMENTS PARTS PROVIDED THROUGH YOUR AUTHORIZED J TUL DEALER 18 19 18 17 14 16 15 20 22 23 24 21 25 26 27 28 29 34 30 31 33 32 29 1 2 3 4 5 6 7 8 9 10 11 12 13 41...

Page 19: ...f C 1 25 therefore R brick 1 C 1 1 25 0 80 1 8 mineral board of k 0 29 therefore R mineral board 1 29 X 0 125 0 431 Total R R brick R mineral board 0 8 0 431 1 231 Step C Compare proposed system R 1 2...

Page 20: ...ue a policy of constant product development Products supplied may therefore differ in specification colour and type of accessories from those illustrated and described in the brochure J tul vise sans...