background image

12

Jøtul GZ 

550

 DV II

Variable Vent Restriction

Vent restriction is accomplished by sliding a restrictor
panel over the combustion air intake ports located at
the back of the firebox. See Fig 19. The panel is set in a
fully open position at the factory. Use the Vent
Window diagrams in Figs. 12-13 as a starting point to
determine the best restriction setting. Follow these
steps to adjust the restriction as necessary:

1.  Remove the Controls Panel to access the adjust-

ment lever at the rear of the valve compatment.
Simply loosen the two wingnuts that secure the
panel to the cabinet floor and pull the panel
forward. You do not need to disconnect any wires.

2. Locate the vent restriction wingnut protruding

from the firebox floor at the rear of the valve
compartment. Loosen the wingnut and push the
lever to the left to increase restriction in one inch
increments, e.g: 1 inch travel = 1/3 closed position.

The ideal restrictor setting for a particular vent

system will vary depending on the specific installa-
tion characteristics. Once the fireplace is operating,
further restrictor adjustment may be necessary to
obtain the best performance. See the Operation
chapter of this manual for more information.

Figure 19. Vent restrictor adjustment.

Fireplace Installation

Optional Blower

Install the optional Blower (155630) before installing
the gas supply line.

Power Requirement

The blower must be electrically grounded in accor-
dance with local codes or, in the absence of local
codes, with the current NFPA 70- National Electrical
Code or CSA C22.1-Canadian Code.

A three-prong (grounding) power supply plug is

included for protection against shock hazard and
should be plugged directly into a properly grounded
three-prong receptacle.      

Blower Function

In the Auto mode, the blower is controlled by a heat
activated switch (snapstat) that will turn the fan on
and off as the firebox heats and cools.  Use the
Manual mode to over-ride the snapstat. If the blower
is not needed, place the blower control switch in the
OFF position and the snapstat will not function.

Installation

1. Loosen the two wingnuts that secure the Control

Panel to the fireplace floor. Pull the panel forward
and swing it to the right to access the rear of the
cabinet. Do not disconnect any wires.

2. Insert a rubber grommet at each corner of the Base

Plate as shown in fig. 20.

3. Engage the Blower unit base with the four studs at

the rear of the fireplace cabinet floor. See fig. 21.

4.  Insert the Snapstat into the slot in the Snapstat Bracket

and, using the M6 nuts and 10 mm socket, attach the
Control Switch / Snapstat Bracket to the two studs
protruding from the firebox floor. See fig. 22.

5. Connect the Blower Wire harness to the switch

connector at the back of the Control Panel. Connect
the two other leads to either terminal on the
snapstat. Attach the green ground wire to the left
Control Panel mounting stud. Replace the Control
Panel and tighten the wingnuts.

6. Run the power cord to the duplex receptacle in the

side of the cabinet. Gather slack cord into the side
cavity, away from the plumbing and other wiring.

f i r e - p a r t s . c o m

Summary of Contents for GZ 550 DV II Acadia

Page 1: ...sult causing property damage personal injury or loss of life QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer l appareil Ne touchez aucum interrupteur Ne pas vous servir des t l phone...

Page 2: ...BE INSTALLED AND MAINTAINED BY A QUALIFIED SERVICE AGENCY IN THE COMMENWEALTH OF MASSACHUSETTS THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER DO NOT ATTEMPTTO ALTER OR MODIFYTHE CO...

Page 3: ...cement 26 Service Log 27 Illustrated Parts Breakdown 28 Replacement Parts List 29 Accessories 30 Lighting Instructions Back Cover Unpacking the Fireplace 1 Before you remove the carton remove the cast...

Page 4: ...fety standards and is tested and listed by Intertek Testing Services of Middleton Wisconsin to ANSI Z21 88 2005 ANSI Z21 88a CSA 22 3a 2007 CAN CGA 2 17 M91 and CSA P 4 01 2 J tul AS Fredrikstad Norwa...

Page 5: ...selon les codes ou reglements locaux ou en l absence de tels reglements selon les Codes d installation CAN CGA B149 4 DO NOT OPERATE THIS FIREPLACE IF ANY PART HAS BEEN UNDER WATER Immediately call a...

Page 6: ...les enfants Garder les vetements les meubles l essence ou autres liquides a vapeur inflammables loin de l appareil Clothing or other flammable materials should not be placed ON or NEAR the Acadia gas...

Page 7: ...N FL ET ON FLO O O O OOR SU OR SU OR SU OR SU OR SUR R R R RF F F F FA A A A AC C C C CE E E E E L L L L LO O O O OW W W W WER ER ER ER ER T T T T THAN HAN HAN HAN HAN T T T T TH H H H HE FR E FR E FR...

Page 8: ...t rock is also considered combustible Maintain the proper clearances to the appliance to allow adequate flow of ventilation air around the fireplace Figure 8 Minimum Wall and Trim Clearance Measuredfr...

Page 9: ...tions n Top 2 51 mm Sides Bottom 1 25 mm 4 6 Pipe 10 x 10 5 8 Pipe 11 x 11 Any horizontal run must rise 1 4 per foot Install venting in accordance with the vent manu facturers instructions Never modif...

Page 10: ...ecific characteristics of your installation may require different settings Horizontal Termination The vent must terminate within the shaded area designated in Figs 15 and 16 Do not Do not Do not Do no...

Page 11: ...ly recommend 12 inches particularly where windy conditions pevail H Not to be installed within 15 feet 4 5 m above a meter regulator assembly within 3 feet 90 cm horizontally from the center line of t...

Page 12: ...local codes or in the absence of local codes with the current NFPA 70 National Electrical Code or CSA C22 1 Canadian Code A three prong grounding power supply plug is included for protection against...

Page 13: ...with the finished surface of the wall facing The stud braces allow approximately 2 inches of forward adjustment to accommodate most any facing thickness Secure the braces to the enclosure frame 5 Com...

Page 14: ...where flexible gas lines are not permitted use the 3 8 iron fitting to make the connection at the left side of the Control Valve See Figures 25 and 26 Secure all joints tightly using appropriate tools...

Page 15: ...T MUST BE INSTALLED BY AN AUTHORIZED SERVICE TECHNICIAN IN ACCOR DANCE WITH THE MANUFACTURER S INSTRUCTIONS AND ALL CODES AND REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION THE INFORMA TION STICKER...

Page 16: ...t is included for conversion to Propane use if desired Check the identification label on the Control Valve to confirm that the correct fuel is used Cet equipement de conversion sera installe par une a...

Page 17: ...tter Wingnut Pull Frame Spring Latch to release Air Shutter Burner Tube Figure 30 Move shutter forward to disengage the burner tube assembly FROM WITHIN THE FIREBOX disengage the Pilot Hood by releasi...

Page 18: ...tor to valve body Apply LABEL A to the cabinet floor so that it may be seen by anyone servicing the fireplace Apply LABEL B to the Rating Plate in the space provided apply gas to the system and check...

Page 19: ...OTHER WIRES See Figure 34 At the thermostat the two wires should be connected to the two connections screw on the thermostat base plate per the manufacturer s instructions For thermostatic function p...

Page 20: ...urner Skirt and against the firebox wall Push the panel forward against the front lip of the firebox opening See fig 39 Orient the panel so that the beveled edge is on top and the mortar joints align...

Page 21: ...Cross over Log 5 with the pin in the Rear Log Fig 42 Set the Cross over Log across the top of the lower end of the Front Log 4 as illustrated 6 6 6 6 6 Spread a layer of ember stones evenly over the...

Page 22: ...oshow thewinter scene Note BlueBlackPanelisenamelledononesideonly 5 5 5 5 5 Hang Hang Hang Hang Hang the C the C the C the C the Cen en en en enter Pla ter Pla ter Pla ter Pla ter Plate in position te...

Page 23: ...control valve This valve provides easy adjust ment of the flame height appearance and heat output To adjust the flame between the HI and LO setting rotate the HI LO knob located in the center of the...

Page 24: ...d to the new setting Retighten the locknut when the desired flame pattern is established 3 Reassemble the fireplace including glass assem bly Allow the fireplace to burn 15 20 minutes on the HIGH sett...

Page 25: ...y allowing plenty of fresh air to circulate through the area Condensation may develop on the glass upon each lighting of the appliance This fog will disappear as the glass heats Keep the controls and...

Page 26: ...east annually Examine the ribbon gasket for signs of deterioration and make sure the gasket has a positive seal Replace the gasket if necessary Refer to the replacement parts list on page 28 Glass Pan...

Page 27: ...____________________________ SERVICE LOG Third Year Name of Technician________________________ Company Name____________________________ Date of service_____________________________ Work Per formed____...

Page 28: ...7 28 29 30 31 32 33 34 35 37 38 39 40 36 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 108 84 85 86 87 88 89 90 91 92 93...

Page 29: ...rround Leg Right Blue Black 10395727 Surround Leg Right J tul Iron 10395785 72 Surround Leg Left Matte Black 10395992 Surround Leg Left Blue Black 10395927 Surround Leg Left J tul Iron 10395985 73 Han...

Page 30: ...ersion Kit LP 155611 Fuel Conversion Kit LP 155594 Fuel Conversion Kit NG 155595 Wall Thermostat 750003 Remote Control 129706 Steel Rectangular Matte Black 154964 Steel Arch Matte Black 154965 Brushed...

Page 31: ...part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 1 1 1...

Page 32: ...the installation it is important that the these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specificatio...

Reviews: