background image

5

Use a hammer to strike the center of the 6” “knock-out” 

disc from the outside of the stove.  The “knock-out” disc 

will break into four wedges and may need to be tapped 

out.  Touch up any remaining sharp edges with a file or 

hand grinder.

Reinstall the top casting and front door with hinge 

washer.  Replace the rear heatshields and shield spacer 

nuts. Remove the metal cover plates from the heatshields 

and reinstall.  

Reminder:

 Reinstall the small nuts used as 

spacers between the two heatshields. See 

fig 2

.

Side-exit Venting

If venting through the side is desired it will be necessary 

to remove the top casting. Using a 3mm allen wrench 

remove the two set screws that secure to the top to the 

side panels.  Remove the  front door to avoid damage to 

the glass.  Reminder:  Loss of the door washer will result 

in improper door alignment when reinstalling the door.
Using a claw hammer or a small sledge hammer strike the 

center of the 6” “knock-out” disc from the inside of the 

stove.  The “knock-out” disc will break into four wedges 

and may need to be tapped out.  Touch up any remaining 

sharp edges with a file or hand grinder.  Reinstall the front 

door, remembering the washer and the top casting.

Installing the flue collar

 

Place the self-adhesive gasket 

(Fig.3A)

 on the underside 

of the smoke outlet 

(Fig. 3B)

.

Mount the smoke outlet with use of the supplied screws 

and cross bar 

(Fig. 3C) 

Secure the first section of stove pipe to the flue collar using 

two sheet metal screws.

USA/Canada

Fig. 2

Spacer 

Nuts

Heatshield with 

listing label should 

be installed on the 

outside

Fig.3

Stove pipe - chimney connector

The chimney connector is a single walled pipe used 

to connect the stove to the chimney.  For use with the  

Jøtul F

3

 the chimney connector must be 6” in diameter, 

with a minimum thickness of 24 gauge black steel.

Aluminum and galvanized steel pipe is not acceptable for 

use with the Jøtul F

3

. These materials cannot withstand 

the extreme temperatures of a wood fire and can give off 

toxic fumes when heated.

Each chimney connector or stove pipe section must be 

installed to the stove flue collar and to each other with 

the male (crimped) end toward the stove.  See 

figure 4

.

Fig. 4

Crimped end installed

toward the stove

This prevents any amount of condensed or liquid creosote 

from running down the outside of the pipe or the stove top. 

All joints must be secured with three sheet metal screws 

to ensure that the sections do not separate.

For the best performance the chimney connector should 

be as short and direct as possible, with no more than two 

90° elbows.  The maximum horizontal run is 36” and a 

recommended total length of stove pipe should not exceed 

10 feet. Always slope horizontal runs upward 1/4” per foot 

toward the chimney.

No part of the chimney connector may pass through an 

attic or roof space, closet or other concealed space, or 

through a floor or ceiling.  All sections of the chimney 

connectors must be accessible for cleaning.  

f i r e - p a r t s . c o m

Summary of Contents for F 3 C

Page 1: ...J tul F 3 CB Installation and Operating Instructions for the USA and Canada 2 Exploded view 20 Kindly save these instructions for future reference J tul F 3 CB Manual Version R14 fire parts com...

Page 2: ...tion Combustion Efficiency 14 Wood Fuel and Performance 14 Air Flow and Controls 15 Break in Procedure 15 Starting and Maintaining a Fire 16 6 0 Maintenance Ash Removal 17 Glass Care 17 7 0 General Ma...

Page 3: ...Default values per previous Federal Register 40 CFR Part 60 Subpart AAA EPA validated efficiency and CO values were unavailable at the time of this printing These values will be made available in the...

Page 4: ...WOOD FUEL ONLY DO NOT BURN ANY OTHER FUEL DO NOT USE CHEMICALS OR FLUIDS TO START A FIRE DO NOT BURN GARBAGE OR FLAMABLE FUELS DO NOT USE A GRATE OR ELEVATE THE FIRE BUILD THE FIRE DIRECTLY ON THE HEA...

Page 5: ...r Fig 3C Secure thefirst sectionofstovepipe to thefluecollarusing two sheet metal screws USA Canada Fig 2 Spacer Nuts Heatshield with listing label should be installed on the outside Fig 3 Stove pipe...

Page 6: ...conform to all of the following guidelines The chimney flue size should not be less than the cross sectional area of the stove flue collar The cross sectional area of the flue of a chimney with no wal...

Page 7: ...onsult with your local building officials to discuss any local code requirements Common method When passing through a combustible wall to a masonry chimney this method requires the removal of all USA...

Page 8: ...round the chimney connector s proposed location With a 6 round liner the minimum area required would be 43 x 43 square It is important to remember to locate the pass through at least 25 from the ceili...

Page 9: ...the proper clearances to surrounding trim and mantels addressed in clearance section of this manual In addition fireplace installations must also adhere to the floor protection guidelines specified in...

Page 10: ...in when installing the J tul F 3 near combustible surfaces A combustible surface is anything that can burn i e Sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are v...

Page 11: ...mm past the ash lip of the stove Must be 1 off the wall and 1 off the floor With standard legs the shield must be 40 high With optional short legs the shield must be 38 high Both shields must extend a...

Page 12: ...17 6 6 6 Double wall pipe or shields 460mm 355mm 430mm 150mm 150mm 150mm Connector Unprotected Surface Protected Surface Clearances per NFPA 211 or CAN CSA B365 M Singlewall pipe vertical installatio...

Page 13: ...015mm Height above the top of the stove 68 1730mm Top vent vertical assumes the connector pipe is exiting off the top of the stove and traveling vertically If top vented to any horizontal runs the sto...

Page 14: ...l burn too quickly to take advantage of the stove s low end efficiency strength A seasoned log will have check marks on the ends and be lighter than an unseasoned log which will show little or no chec...

Page 15: ...mid range position to allow adequate oxygen to support efficient combustion throughout the burn cycle Fig 16 Stove top thermometer 5 5 Break In Procedure The J tul F 3 CB is constructed of cast iron a...

Page 16: ...ESULT IN PERMANENT DAMAGE TO THE HEATER Creosote and Soot Formation and the Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to...

Page 17: ...l F 3 Do not use substitutes Replacement glass panels can be ordered through your J tul dealer Glass removal Always operate the doors slowly and cautiously to avoid cracking or breaking the glass Neve...

Page 18: ...e a utility light to inspect the stove inside and out for cracks or leaks Replace all cracked parts and repair any cement leaks with furnace cement Fig 17 Door Gasket Glass Glass clips Gaskets Door an...

Page 19: ...or protection with a minimum insulating R value of 1 1 Alcove installation require a minimum R value of 1 1 If a UL ULC 8 0 Accessories Firescreen 350168 TheJ tulF3hasbeenapprovedforuseasanopenfirepla...

Page 20: ...8 4 7 6 5 12 9 8 16 15 4 42 39 41 40 38 37 35 33 34 31 32 30 26 28 29 27 5 23 24 18 17 5 22 65 70 72 71 4 64 81 60 5 7 10 5 13 19 14 20 11 50 4 48 79 79 84 313 0 87 88 89 66 69 4 90 91 92 93 94 95 2c...

Page 21: ...lip 52 Leg 53 Skrew M6x20 ST 8 8 ubeh 54 Washer 18x0 6 4x1 55 Bottom plate 57 Inner bottom plate 58 Screw sink head M6x25 sortkrom poz black poz 59 Burn plate left 60 Insulation Firemaster blanket af...

Page 22: ...le and is extended only to and is solely for the benefit of the original retail purchaser of the J tul or Scan Stove or Fireplace Insert This paragraph sets forth the sole remedy available under this...

Page 23: ...reach of this warranty shall be limited exclusively to the cost of furnishing a replacement component J TUL may at its discretion discharge all obligations by refunding the wholesale price of any defe...

Page 24: ...result of J tul s vast experience dating back to when the company first started in 1853 We appreciate your trust in welcoming our product into your home and invite your comment and appraisal of our e...

Reviews: