background image

10

4.0 Clearances to combustibles

Floor Protection

Floor protection under the Jøtul F 

3

, must be one of the 

following:

1.   Any non combustible material with an insulative  

R value of 1.1.

2.   Any UL, ULC or WH hearth board.  

The bottom heatshield (standard equipment) is required 

in all installations.

Individual sections of floor protection must be mortared 

together t,o prevent sparks from falling through to 

combustible materials.  Any carpeting must be removed 

from under the floor protection.

In the U.S.and Canada

The Jøtul F 

3

 must be installed on a non-combustible 

surface extending a minimum of 16” for U.S. (46 cm 

for Canada) in front of the stove and 8” (20 cm) on the 

remaining sides of the stove (measured from side and 

back panels).

 

This will result in a minimum floor protection of 39 cm D 

x 39 cm W. for U.S.,and 104 cm D x 99 cm W for Canada.

See 

figure 12

.

In a rear vent installation the floor protection must also 

extend under the stove pipe a minimum of 2” (5 cm) beyond 

either side of the pipe.

Fig. 12

2

(

5

 cm)

39

” U.S

(

104

 cm Can)

39

” U.S.

(

99

 cm Can)

Hearth Protection

A: 

8

” (

20

 cm)

B: 

16

” for U.S. (

46

 cm for Canada)

B

A

A

A

USA/Canada

Clearances to walls and ceilings

The following clearances have been tested to UL and ULC 

standards and are the minimum clearances specifically 

established for the Jøtul F 

3

(See next page)

The following charts and diagrams give the required 

clearances you must maintain when installing the  

Jøtul F 

3

 near combustible surfaces. 

A combustible surface is anything that can burn (i.e. Sheet 

rock, wall paper, wood, fabrics etc.). These surfaces are not 

limited to those that are visible and also include materials 

that are behind non-combustible materials.  

If you are not sure of the combustible nature of a material, 

consult your local fire officials.  

Remember:

 “Fire resistant” materials are considered 

combustible; they are difficult to ignite, but will burn.  

Also “fire-rated” sheet rock is also considered combustible.

Contact your local building officials about restrictions and 

installation requirements in your area.

Using shields to reduce clearances

Pipe shields: When using listed pipe shields to reduce 

the connector clearance to combustibles, it must start 1” 

above the lowest exposed point of the connect pipe and 

extend vertically a minimum of 25” above the top surface 

of the stove.

Double wall pipe: Listed double wall pipe is an acceptable 

alternative to connector pipe heatshields.

Wall-mounted protection: When reducing clearances 

through the use of wall mounted protection:

In the U.S. Refer to NFPA 211, standard for chimneys, 

fireplaces, vents and solid fuel burning appliances, for 

acceptable materials, proper sizing and construction 

guidelines. 

In Canada, refer to CAN/CSA-B365, installation code for 

solid-fuel burning appliances and equipment, also for 

acceptable materials, proper sizing and construction 

guidelines.

Stove mounted rear heatshield is standard equipment 

on all Jøtul F 

3

`s.  

No   other   stove  mounted heat  shield   

may  be used.

f i r e - p a r t s . c o m

Summary of Contents for F 3 C

Page 1: ...J tul F 3 CB Installation and Operating Instructions for the USA and Canada 2 Exploded view 20 Kindly save these instructions for future reference J tul F 3 CB Manual Version R14 fire parts com...

Page 2: ...tion Combustion Efficiency 14 Wood Fuel and Performance 14 Air Flow and Controls 15 Break in Procedure 15 Starting and Maintaining a Fire 16 6 0 Maintenance Ash Removal 17 Glass Care 17 7 0 General Ma...

Page 3: ...Default values per previous Federal Register 40 CFR Part 60 Subpart AAA EPA validated efficiency and CO values were unavailable at the time of this printing These values will be made available in the...

Page 4: ...WOOD FUEL ONLY DO NOT BURN ANY OTHER FUEL DO NOT USE CHEMICALS OR FLUIDS TO START A FIRE DO NOT BURN GARBAGE OR FLAMABLE FUELS DO NOT USE A GRATE OR ELEVATE THE FIRE BUILD THE FIRE DIRECTLY ON THE HEA...

Page 5: ...r Fig 3C Secure thefirst sectionofstovepipe to thefluecollarusing two sheet metal screws USA Canada Fig 2 Spacer Nuts Heatshield with listing label should be installed on the outside Fig 3 Stove pipe...

Page 6: ...conform to all of the following guidelines The chimney flue size should not be less than the cross sectional area of the stove flue collar The cross sectional area of the flue of a chimney with no wal...

Page 7: ...onsult with your local building officials to discuss any local code requirements Common method When passing through a combustible wall to a masonry chimney this method requires the removal of all USA...

Page 8: ...round the chimney connector s proposed location With a 6 round liner the minimum area required would be 43 x 43 square It is important to remember to locate the pass through at least 25 from the ceili...

Page 9: ...the proper clearances to surrounding trim and mantels addressed in clearance section of this manual In addition fireplace installations must also adhere to the floor protection guidelines specified in...

Page 10: ...in when installing the J tul F 3 near combustible surfaces A combustible surface is anything that can burn i e Sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are v...

Page 11: ...mm past the ash lip of the stove Must be 1 off the wall and 1 off the floor With standard legs the shield must be 40 high With optional short legs the shield must be 38 high Both shields must extend a...

Page 12: ...17 6 6 6 Double wall pipe or shields 460mm 355mm 430mm 150mm 150mm 150mm Connector Unprotected Surface Protected Surface Clearances per NFPA 211 or CAN CSA B365 M Singlewall pipe vertical installatio...

Page 13: ...015mm Height above the top of the stove 68 1730mm Top vent vertical assumes the connector pipe is exiting off the top of the stove and traveling vertically If top vented to any horizontal runs the sto...

Page 14: ...l burn too quickly to take advantage of the stove s low end efficiency strength A seasoned log will have check marks on the ends and be lighter than an unseasoned log which will show little or no chec...

Page 15: ...mid range position to allow adequate oxygen to support efficient combustion throughout the burn cycle Fig 16 Stove top thermometer 5 5 Break In Procedure The J tul F 3 CB is constructed of cast iron a...

Page 16: ...ESULT IN PERMANENT DAMAGE TO THE HEATER Creosote and Soot Formation and the Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to...

Page 17: ...l F 3 Do not use substitutes Replacement glass panels can be ordered through your J tul dealer Glass removal Always operate the doors slowly and cautiously to avoid cracking or breaking the glass Neve...

Page 18: ...e a utility light to inspect the stove inside and out for cracks or leaks Replace all cracked parts and repair any cement leaks with furnace cement Fig 17 Door Gasket Glass Glass clips Gaskets Door an...

Page 19: ...or protection with a minimum insulating R value of 1 1 Alcove installation require a minimum R value of 1 1 If a UL ULC 8 0 Accessories Firescreen 350168 TheJ tulF3hasbeenapprovedforuseasanopenfirepla...

Page 20: ...8 4 7 6 5 12 9 8 16 15 4 42 39 41 40 38 37 35 33 34 31 32 30 26 28 29 27 5 23 24 18 17 5 22 65 70 72 71 4 64 81 60 5 7 10 5 13 19 14 20 11 50 4 48 79 79 84 313 0 87 88 89 66 69 4 90 91 92 93 94 95 2c...

Page 21: ...lip 52 Leg 53 Skrew M6x20 ST 8 8 ubeh 54 Washer 18x0 6 4x1 55 Bottom plate 57 Inner bottom plate 58 Screw sink head M6x25 sortkrom poz black poz 59 Burn plate left 60 Insulation Firemaster blanket af...

Page 22: ...le and is extended only to and is solely for the benefit of the original retail purchaser of the J tul or Scan Stove or Fireplace Insert This paragraph sets forth the sole remedy available under this...

Page 23: ...reach of this warranty shall be limited exclusively to the cost of furnishing a replacement component J TUL may at its discretion discharge all obligations by refunding the wholesale price of any defe...

Page 24: ...result of J tul s vast experience dating back to when the company first started in 1853 We appreciate your trust in welcoming our product into your home and invite your comment and appraisal of our e...

Reviews: