3
Check Building Codes
When installing, operating and maintaining your
Jøtul F
3
CB woodstove, follow the guidelines presented
in these instructions, and make them available to anyone
using or servicing the stove.
Your city, town, county or province may require a building
permit to install a solid fuel burning appliance.
In the U.S.,
the National Fire Protection Association’s Code,
NFPA 211,
Standards for Chimneys, Fireplaces, Vents and
Solid Fuel Burning Appliances
, or similar regulations, may
apply to the installation of a solid fuel burning appliance
in your area.
In Canada
, the guideline is established by the CSA
Standard, CAN/CSA-B365-M93,
Installation Code for Solid-
Fuel-Burning Appliances and Equipment.
Always consult your local building inspector or authority
having jurisdiction to determine what regulations apply
in your area.
USA/Canada
Standards
The Jøtul F
3
CB solid fuel heater has been tested and
listed to :
U.S. Standards: ANSI/UL 737 and ANSI/UL 1482.
Canadian Standards:
CAN/ULC-S627-M
00
and CAN/ULC-S628-M
93
Certified Safety Tests performed by:
Intertek Testing Services, Middleton, Wisconsin U.S.A.
Manufactured by:
Jøtul AS
P.O. Box 1411, Fredrikstad, Norway
and
Jøtul North America, Inc.
55 Hutcherson Drive
Gorham, Maine 04038, USA
Combustion Specifications
Heat Output*:
Under specific test conditions, this
heater has been shown to deliver heat ranging from
11,400 to 43,500 BTU’s
.
Efficiency*:
63%
CO Emissions:
N/A
Pariculate Emissions:
3.8 g/h
* Default values per previous Federal Register 40 CFR Part
60, Subpart AAA.
EPA validated efficiency and CO values were unavailable
at the time of this printing. These values will be made
available in the manual and on the Jotul website (www.
jotul.us) for your reference in the near future.
Installation and
Operation Instructions
for North America
Safety Notice: If this solid fuel room heater is not properly
installed, a house fire may result. For your safety, follow
the installation directions. Contact local building or fire
officials about restrictions and installation inspection
requirements in your area.
This manual describes the installation and operation of
the Jøtul F 3 CB non-catalytic wood heater. Read this entire
manual before you install and use your new stove. Save
these instructions for future reference.
This wood heater needs periodic inspection and repair for
proper operation. See this manual for specific information.
It is against federal regulations to operate this wood
heater in a manner inconsistent with the operating
instructions in this owner’s manual.
This heater meets the
2015
U.S.
Environmental Protection Agency’s
emission limits for wood heaters
manufactured after May 15, 2015.
This heater may not to be sold after
May 15, 2020.
WARNING !
THIS WOOD HEATER HAS A MANUFACTURER-
SET MINIMUM LOW BURN RATE THAT MUST
NOT BE ALTERED. IT IS AGAINST FEDERAL
REGULATIONS TO ALTER THIS SETTING
OR OTHERWISE OPERATE THIS WOOD
HEATER IN A MANNER INCONSISTENT WITH
OPERATING INSTRUCTIONS IN THIS MANUAL.
See Sect. 5.0 of this manual for important information
regarding the safe, proper, and most efficient operation
of your stove.