82
ENGLISH
Fig. 4b
3. If a rear outlet is used, the upper middle part of the
heatshield is removed. This is done by cutting o
ff
4 metal
studs (cutters should be used).
Assembly of the
fl
ue pipe
The product is assembled for a top outlet as standard.
Fig. 5 Assembling the
fl
ue pipe
B
A
C
1. Attach the gasket (B) to the end of the
fl
ue pipe(A). Then
insert the
fl
ue pipe into the outlet (C).
Flue pipe is installed in the same way for top and rear outlet.
4.3 Assembly with an external air
supply (optional extra - 51047509)
Fresh air supply
The air used for combustion in any well-insulated house needs
to be replaced. This is particularly important in houses with
mechanical ventilation. Such replacement air can be procured
in several ways. The most important thing is to supply the air
to the room where the stove is placed. Place the outside wall
valve as close to the stove as possible and make sure that it
can be closed when the stove is not in use.
For the fresh air supply connection, follow the national and
local building regulations.
Important!
Ensure that air vents in the room where the
fi
replace is located are not blocked.
Closed combustion system
Use the stove’s closed combustion system if you live in recently
built, airtight dwellings. Connect the external combustion air
through a ventilation pipe through the wall or the
fl
oor.
Air supply
The amount of combustion air for Jøtul’s products is approximately
20-40 m
3
/h. The outside air connection may be
fi
tted directly to
the Jøtul F 200/F 205 through:
• the
bottom
• through
a
fl
exible supply hose from the outside/chimney
(only if the chimney has its own duct for external air) and to
the product’s outside air connector.
Fig. 6a Through an outside wall
Summary of Contents for F 200
Page 20: ...20...
Page 38: ...38...
Page 56: ...56...
Page 74: ...74...
Page 92: ...92...
Page 110: ...110 FRANCAIS...
Page 145: ...145 ITALIANO...
Page 146: ...146...
Page 164: ...164 DEUTSCHLAND...